Page 1
Application Note 9PX5KP1 and 9PX6KP1 interconnect diagram The following steps outline how to properly interconnect the 9PX5KP1 and 9PX6KP1. Each of these models is a bundle which contains a UPS and a PPDM. The UPS is an Uninterruptible Power Supply which contains power electronics and batteries. The PPDM is a PowerPass Distribution Module which contains a wrap‐around maintenance bypass, a step down transformer for 120V output, and output distribution (receptacles and breakers). UPS “Normal AC Source” Input Cable PPDM PPDM “From UPS Output” Cable PPDM “Normal AC Source” Input Cable Figure 1. UPS and PPDM before interconnecting 1. Step 1: Ensure proper alignment. For rackmount applications the UPS and PPDM should be installed adjacent to one another. This will ensure that the interconnect cables will be able to properly make the connections. Likewise, installations in the tower position should be adjacent using the steps ...
Page 2
Figure 2. UPS and PPDM after Step 2 3. Step 3: Connect the UPS “Normal AC Source” Input Cord on the UPS to the PPDM 30A, L6‐30 receptacle labeled To UPS INPUT. Note that the UPS input cord is 6 ft (1.8m) long and is shown shorter in the diagram to simplify. UPS “Normal AC Source” Input Cable PPDM “From UPS Output” Cable PPDM PPDM “Normal AC Source” Input Cable Figure 3. UPS and PPDM after Step 3 4. Step 4. Connect the PPDM “Normal AC Source” Input Cable to the local L6‐30R utility source. Note that the UPS input cord is 6ft (1.8m) long and is shown shorter in the diagram to simplify. AP153003EN www.eaton.com/9PX July 2014...