Interconnect diagram

Advertisement

Quick Links

9PX5KP1 and 9PX6KP1 interconnect diagram
The following steps outline how to properly interconnect the 9PX5KP1 and 9PX6KP1. Each of these models is a bundle 
which contains a UPS and a PPDM. The UPS is an Uninterruptible Power Supply which contains power electronics and 
batteries. The PPDM is a PowerPass Distribution Module which contains a wrap‐around maintenance bypass, a step down 
transformer for 120V output, and output distribution (receptacles and breakers). 
UPS
PPDM
Figure 1. UPS and PPDM before interconnecting
1. Step 1: Ensure proper alignment. For rackmount applications the UPS and PPDM should be installed 
adjacent to one another. This will ensure that the interconnect cables will be able to properly make 
the connections. Likewise, installations in the tower position should be adjacent using the steps 
shown in Chapter 3 of the Eaton 9PX PowerPass® Distribution Modules and Transformers 
9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide. 
 
2. Step 2: Connect the "From UPS Output" Cable on the PPDM to the UPS. The cable should connect to 
one of the 30A, L6‐30 receptacles.  
AP153003EN
PPDM "Normal AC Source"
Input Cable
www.eaton.com/9PX
Application
Note
UPS "Normal AC Source"
Input Cable
PPDM "From UPS Output"
Cable
July 2014

Advertisement

loading

Summary of Contents for Eaton 9PX5KP1

  • Page 1 Application Note 9PX5KP1 and 9PX6KP1 interconnect diagram The following steps outline how to properly interconnect the 9PX5KP1 and 9PX6KP1. Each of these models is a bundle  which contains a UPS and a PPDM. The UPS is an Uninterruptible Power Supply which contains power electronics and  batteries. The PPDM is a PowerPass Distribution Module which contains a wrap‐around maintenance bypass, a step down  transformer for 120V output, and output distribution (receptacles and breakers).  UPS “Normal AC Source” Input Cable PPDM PPDM “From UPS Output” Cable PPDM “Normal AC Source” Input Cable Figure 1. UPS and PPDM before interconnecting 1. Step 1: Ensure proper alignment. For rackmount applications the UPS and PPDM should be installed  adjacent to one another. This will ensure that the interconnect cables will be able to properly make  the connections. Likewise, installations in the tower position should be adjacent using the steps ...
  • Page 2 Figure 2. UPS and PPDM after Step 2 3. Step 3: Connect the UPS “Normal AC Source” Input Cord on the UPS to the PPDM 30A, L6‐30  receptacle labeled To UPS INPUT. Note that the UPS input cord is 6 ft (1.8m) long and is shown  shorter in the diagram to simplify.  UPS “Normal AC Source” Input Cable PPDM “From UPS Output” Cable PPDM PPDM “Normal AC Source” Input Cable Figure 3. UPS and PPDM after Step 3 4. Step 4. Connect the PPDM “Normal AC Source” Input Cable to the local L6‐30R utility source. Note  that the UPS input cord is 6ft (1.8m) long and is shown shorter in the diagram to simplify.  AP153003EN www.eaton.com/9PX July 2014...