Eaton 9PX6KIRTN-L User Manual page 47

9px 6kva lithium-ion
Table of Contents

Advertisement

Table 14. Environmental and Safety
Certifications
EMC ( Emissions)*
EMC (Immunity)
* for output cable < 10m.
Agency Markings
Operating Temperatures
Storage Temperatures
Transit Temperature
Relative Humidity
Operating Altitude
Transit Altitude
Audible Noise
Table 15. Battery
Rack / Tower configuration
Type
EN/IEC 62040-1
EN/IEC 62040-2
EN/IEC 62040-3
UL1778 5th edition
CSA 22.2
CISPR32 (EN55032) Class A
AS/NZS CISPR32 Class A
IEC 61000 -3-11
IEC 61000 -3-12
FCC part 15 Class A
IEC 61000-2-2
IEC 61000-4-2, Level 3
IEC 61000-4-3, Level 3
IEC 61000-4-4, Level 4 (also on signal ports)
IEC 61000-4-5, Level 4, Criteria B
IEC 61000-4-6, Level 3
IEC 61000-4-8, Level 4
IEC 61000-4-12
CE cULus ; UKCA; RCM; Ukr; EAC; Cmim
0 to 40°C (32 to 104°F) in Online mode, with linear derating for
altitude
Note: thermal protection switches load to Bypass in case of
overheating.
0 to 40°C (32 to 104°F) with batteries
-15 to 60°C (5 to 140°F) without batteries
-25 to 55°C (-13 to 130°F)
0 to 95% no condensing
Up to 3,000 meters (9,843 ft) above sea level with 10% derating
per 1000m
Up to 10,000 meters (32,808 ft) above sea level
< 45 dBA at 1 meter typical
UPS enclosure IP rating: IP20
Protective class: Class I
Power system: TN/TT/IT
Internal Batteries
9PX6KIRTN-L: 192Vdc
Lithium Iron Phosphate (LFP) battery module
Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01
Model Specifications EMEA
EBM
9PXEBM192RT2U-L: 192Vdc
41

Advertisement

Table of Contents
loading

This manual is also suitable for:

9pxebm192rt2u-l

Table of Contents