Maico ER 60 E Mounting And Operating Instructions page 41

Recess-mounted exhaust air system
Hide thumbs Also See for ER 60 E:
Table of Contents

Advertisement

22. Wiring diagrams
ER 60 EH, ER 100 EH
Standard switching:
ER 60 EH, ER 100 EH
Switching option 1
34
ER 60 EH, ER 100 EH
For function of the humidity control
 chapter 14.1.
The humidity variant must not be
deactivated using a switch on terminal
1 and/or terminal N.
Standard switching:
Permanent base load operation
The fan is running in base load operation,
humidity control is active.
If there is a rapid increase in humidity and the
reference value is exceeded, the fan
automatically switches into full load operation.
The fan switches automatically back to base
load operation if the relative humidity falls
below the reference value.
Switching option 1: Permanent base load
operation with pre-defined overrun time
The fan is running in base load operation.
Humidity control is active, see Standard
Switching.
Switch "S1" is used to switch manually to full
load operation. After switching full load
operation off with "S1", the fan continues in
full load operation for an overrun time of
15 minutes.
If after this time, the humidity as measured at
the fan
● is higher than the reference value, the fan
continues to run in full load operation until
the humidity drops below the reference
value. Only then does the fan switch
automatically back to base load operation.
Is lower than the reference value, the fan
immediately switches automatically back
to base load operation.