Using Test Mode - Mitsubishi Electric ME96SSHA-MB User Manual

Electronic multi-measuring instrument
Hide thumbs Also See for ME96SSHA-MB:
Table of Contents

Advertisement

4. Using Test Mode

Test mode includes functions that can be used for start-up of equipment.
The following table shows what can be done in the test mode.
Test menu
1.
Communication test
2.
Alarm output/Digital output
operation test
3.
Zero span adjustment for
analog output
4.
Analog output operation test
5.
Pulse output operation test
Test Procedure
Press
for 2 seconds to move to the set value confirmation mode.
Select setting value confirmation menu number "9" by
Press
to move to test mode.
Execute tests using each test menu. (Refer to pages 58 to 62)
Test Mode Flow
Setting value
Confirmation
menu "9"
Test menu
End
Note
Operation
mode
(Note) The screen momentarily turns off.
When moving the test mode, ME-0000BU-SS96 becomes power outage state not to be logging the test data.
Note
Therefore, the system log of "Power failure occurred" is recorded in ME-0000BU-SS96 and COM of the LCD is
blinking.
For models with a communication function, it is possible to monitor fixed numerical
data without measurement (voltage/current) input. Use this for checking with the host
system.
For functions with alarm output, it is possible to confirm alarm output (digital point
output) without measurement (voltage/current) input. Use this for confirming
connection with the contacted device.
For functions with analog output, zero span adjustment can be done for analog output.
Adjust this when matching with the receiver side and when output changes.
For functions with analog output, it is possible to confirm analog output operation
without measurement (voltage/current) input. Use this for confirming connection with
the receiver.
For functions with pulse output, it is possible to confirm pulse output operation without
measurement (voltage/current) input. Use this for confirming connection with the
receiver.
Test mode
Test menu 1
(Communication
test)
Test menu 5
(Pulse output
operation test)
Description
and
.
Test menu 2
(Alarm output /Digital
output operation test)
動作テスト)
Test menu 4
(Analog output
operation test)
57
Test menu 3
(Zero span adjustment
for analog test)

Advertisement

Table of Contents
loading

Table of Contents