The Flue Spigot - Valor Black Beauty Slimline Installation And Owner's Manual

Live fuel effect gas fire
Table of Contents

Advertisement

Figure 3. Combustible shelf clearances

5.8 The Flue spigot.

5.8.1 The flue spigot and any spigot extension
must be capable of passing through the closure
plate by at least 15mm with a minimum clearance
of 50mm between its open end and the nearest
obstruction.
There must also be a minimum clearance of
165mm between the back of the closure plate and
the back of the catchment space.
On conventional flues the catchment space below
the flue spigot must extend at least 250mm
downward measured from the bottom of the flue
spigot (See figure 4).
5.8.2 A spigot extension is available (Valor Fires
part number 0595191). When fitted this shall
extend through the closure plate for at least 15mm
and have a minimum clearance of 50mm from the
end to any surface.
©
GDC Group Ltd. JAN 2017
INSTALLER GUIDE
Page 13
Figure 4. Fireplace catchment
space.

Advertisement

Table of Contents
loading

This manual is also suitable for:

341053410105347a1

Table of Contents