F: Inspection
Check the quality of expanding port. If there is any blemish, expand the port
again according to the steps above.

SPECIALIST'S MANUAL

• Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit
without ensuring that this will not exceed the permissible voltage and current
permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked on while
live in the presence of a fl ammable atmosphere. The test apparatus shall be
at the correct rating.
Replace components only with parts specifi ed by the manufacturer. Other
parts may result in the ignition of refrigerant in the atmosphere from a leak.
• Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure,
vibration, sharp edges or any other adverse environmental effects. The check
shall also take into account the effects of aging or continual vibration from
sources such as compressors or fans.
• Detection of fl ammable refrigerants
Under no circumstances shall potential sources of ignition be used in the
searching for or detection of refrigerant leaks. A halide torch (or any other
detector using a naked fl ame) shall not be used.
• Leak detection methods
Leak detection fl uids are suitable for use with most refrigerants but the use of
detergents containing chlorine shall be avoided as the chlorine may react with
smooth surface
leaning damaged
the length is
equal
improper expanding
crack
uneven
surface
thickness
54