Contents Part 1 General Information ................... Part 2 Indoor Units ......................Part 3 Outdoor Units ..................... Part 4 Electrical Control System ................. ※The specifications, designs, and information in this book are subject to change without notice for product improvement. Contents...
Page 3
General Information Part 1 General Information 1. Model Lists ....................2 2. Features ......................4 General Information...
Model Lists 1. Model Lists 1.1 Indoor Units Capacity multiplied by 1000Btu/h R410A Type Function Super-slim four-way cassette Cooling and heating generation ceiling & floor Cooling and heating Duct Cooling and heating floor-standing Cooling and heating General Information...
Features 2. Features 2.1 Universal outdoor unit design Indoor unit with the same capacity can match with the same outdoor unit. 2.2 High efficiency and energy saving. Thanks to the DC inverter technology and optimized piping system, the EER and COP of whole series can easily reach A-class.
Indoor Units Part 2 Indoor Units Super Slim Cassette Type ............ Duct Type ................ Ceiling & Floor Type ............ GA Floor-standing Type ............. Super Slim Cassette Type...
Super Slim Cassette Type Super Slim Cassette Type Features ....................8 Dimensions ..................12 Service Space ..................13 Wiring Diagrams .................. 14 Air Velocity and Temperature Distributions(Reference Data) ..15 Electric Characteristics...............
Page 8
Features 1. Features Overview Compact design, super slim body size, less space requiring in installation Each louver can be separately controlled, more comfort air blowing is possible. Auto-lifting panel design, more convenient to clean and maintain the filter. (optional) Old Cassette New slim cassette Volume change...
Page 9
Features New air-intake Optional ionizer generator Ionizer generator is optional to get refreshing air to your room. Ionizer can be switched on or off by remote controller. When pressing the Clean Air button on the remote controller, Ionizer will work and the indicator light on display board will shine.
Page 10
Features External air duct design Reserve external air duct, more flexible for the air supply. Built-in draining pump Due to the improvement of structure, more convenient to repair or replace the draining pump. Draining Pump Built-in draining pump to make sure condensed water drain out reliably. Super Slim Cassette Type...
Page 11
Features Terminals for alarm lamp and long-distance on-off controller connection are standard Reserve terminals for the connection of alarm lamp and long-distance on-off controller, more human control. Alarm lamp Long-distance on-off controller Optional touch screen wired controller Touch screen wired controller is optional, with error code indication function. Better man-machine conversation interface.
Electric Characteristics 6. Electric Characteristics Indoor Unit Power Supply Model Voltage CCCT140IUINV 220-240 CCT160IUINV 220-240 Notes: MFA: Max. Fuse Amps. (A) Super Slim Cassette Type...
The Specification of Power 9. The Specification of Power 48000-60000 Model(Btu/h) Phase 1-phase Frequency and 220-240V, 50Hz Voltage INDOOR UNIT Power Wiring POWER 3×1.0 Circuit Breaker/Fuse 15/10 3-phase Phase Frequency and 380-415V, 50Hz Voltage OUTDOOR UNIT Power Wiring POWER 3×4.0 Circuit Breaker/Fuse 40/35 Indoor/Outdoor Connecting Wiring...
Page 20
Duct Type Duct Type 1. Features ......................22 2. Dimensions ....................25 3. Service Space ....................26 4. Wiring Diagrams ................... 27 5. Static Pressure ..................... 28 6. Electric Characteristics ................29 7. Sound Levels ....................30 8. Accessories ....................31 9.
Features 1. Features 1.1 Installation accessories: (Optional) Front Board, Canvas Air Passage, Filter, Panel, for easy installation Front Board Canvas Air Passage Filter Panel 1.2 Easy Installation: Two air inlet styles (Bottom side or Rear side) Air inlet from rear is standard for all capacity; air inlet from bottom is optional. ...
Page 22
Features Replace the motor or centrifugal fan Remove the ventilated panel firstly. Remove a half of blower housing and take out the motor with centrifugal fan. Directly remove two bolts, and then replace the motor or centrifugal fan easily. Motor Blower Housing Ventilated Panel...
Page 23
Features 1.7 Built-in display board The standard indoor unit can be controlled by wired controller. There is a display board with a receiver in the E-box. Move out the display, and fix it in other place, even in the distance of 10m. The unit will realized remoter control. ...
Service Space 3. Service Space Ensure enough space required for installation and maintenance. All the indoor units reserve the hole to joint the fresh air pipe. The hole size as following: Duct Type...
Electric Characteristics 6. Electric Characteristics Indoor Unit Power Supply Model Voltage Min. Max. DCT140IUINV 220-240 DCT160IUINV 220-240 Notes: MFA: Max. Fuse Amps. (A) Duct Type...
Accessories Accessories Name Shape Quantity Soundproof / insulation sheath Tubing & Fittings Binding tape Seal sponge Drain joint Drainpipe Fittings (for cooling & heating) Seal ring Wired controller Wired controller & Its Frame Owner , s manual Others Installation manual Magnetic ring (twist the electric wires L EMS &...
The Specification of Power 9. The Specification of Power Model(Btu/h) 48000 60000 48000-60000 Phase 1-phase 1-phase 1-phase Frequency and 220-240V, 50Hz 220-240V, 50Hz 220-240V, 50Hz Voltage INDOOR UNIT Power Wiring POWER 3×1.0 3×1.0 3×1.0 Circuit Breaker/Fuse 15/10 15/10 15/10 Phase 3-phase Frequency and 380-415V, 50Hz...
Page 33
Ceiling & Floor Type Ceiling & Floor Type Features ....................35 Dimensions ..................36 Service Space ..................37 Wiring Diagrams .................. 38 Electric Characteristics............... 39 Sound Levels ..................40 ...
Features 1. Features 1.1. New design, more modern and elegant appearance. 1.2. Convenient installation --The ceiling type can be easily installed into a corner of the ceiling even if the ceiling is very narrow --It is especially useful when installation of an air conditioner in the center of the ceiling is impossible due to a structure such as one lighting.
Electric Characteristics 5. Electric Characteristics Indoor Units Power Supply Model Voltage Min. Max. CFT140IUINV 220-240V 198V 242V CFT160IUINV 220-240V 198V 242V Note: MFA: Max. Fuse Amps. (A) Ceiling & Floor Type...
Page 40
The Specification of Power 8. The Specification of Power Model(Btu/h) 48000 60000 48000-60000 Phase 1-phase 1-phase 1-phase Frequency and 220-240V, 50Hz 220-240V, 50Hz 220-240V, 50Hz Voltage INDOOR UNIT Power Wiring POWER 3×1.0 3×1.0 3×1.0 Circuit Breaker/Fuse 15/10 15/10 15/10 Phase 3-phase Frequency and 380-415V, 50Hz...
Page 41
Field Wiring Field Wiring Ceiling & Floor Type...
GA Floor-standing Type GA Floor-standing Type 1. Features ................错误!未定义书签。 2. Dimensions ................. 错误!未定义书签。 3. Service Space ..............错误!未定义书签。 4. Wiring Diagrams ..............错误!未定义书签。 5.Air Velocity and Temperature distributions(Reference Data) ... 错误!未定义书 签。 6. Electric Characteristics ............错误!未定义书签。 7. Sound Levels ..............错误!未定义书签。 8. Accessories ................ 错误!未定义书签。 9. The Specification of Power ..........
Page 43
Features Features 1.1. Fashionable design, more modern and elegant appearance. 1.2. Air Outlet Dustproof When turned off, the air outlet louver of the unit can be closed manually to prevent the dust falling in. 1.3. Simple and bright panel Adopts simple and bright style panel, GA series are suitable for most different space, and show in good taste.
Page 47
Air Velocity and Temperature Distrib 5. Air Velocity and Temperature Distributions(Reference Data) Model 48K-60K: Airflow velocity Temperature GA Floor-standing Type...
Page 48
Electric Characteristics 6. Electric Characteristics Indoor Units Power Supply Model Voltage Min. Max. FS140IUINV______ 380-420V 342V 440V FS160IUINV______ 380-420V 342V 440V Note: MFA: Max. Fuse Amps. (A) GA Floor-standing Type...
Page 49
Sound Levels Sound Levels Noise level dB(A) Model FS140IUINV______ FS160IUINV______ GA Floor-standing Type...
Page 50
Accessories Accessories Part Name Shape Quantity Safety Lock Self-tapping Screw 3.9×25 Flat Washers Bushing-Sleeve Cover Sound/Heat Insulation Sleeves Seal Drain joint Pipe - hole - protection Ring Remote Battery Remote Controller Connection Cables Remote controller manual User's manual Installation manual GA Floor-standing Type...
Page 51
The Specification of Power 9. The Specification of Power FS140IUINV Model FS160IUINV Phase Frequency and Voltage INDOOR UNIT POWER POWER WIRING (mm CIRCUIT BREAKER (A) Phase 3-phase Frequency and Voltage 380-420V, 50Hz OUTDOOR UNIT POWER POWER WIRING (mm 5×2.5 CIRCUIT BREAKER (A) Indoor/Outdoor Connecting Wiring(Weak Electric Signal) (mm 3×0.5 Indoor/Outdoor Connecting Wiring(Strong Electric Signal) (mm...
Page 52
Outdoor Units Part 3 Outdoor Units 1. Dimensions ..................66 2. Service Space ..................67 3. Piping Diagrams ................. 68 4. Wiring Diagrams ................69 5. Electric Characteristics ..............71 6. Operation Limits................. 72 7. Sound Levels ..................73 Outdoor Units...
Service Space Service Space (Wall or obstacle) More than 30cm Air inlet More than 60cm More than 30cm Maintain channel Air inlet More than 60cm Air outlet More than 200cm Outdoor Units...
Operation Limits Operation Limits Temperature Cooling operation Heating operation Mode Room temperature ≤30℃ ≥17℃ 0℃~50℃ (-15℃~50℃:For Outdoor temperature -15℃~24℃ the models with low temperature cooling system) CAUTION: 1. If the air conditioner is used beyond the above conditions, certain safety protection features may come into operation and cause the unit to operate abnormally.
Sound Levels Sound Levels Outdoor Unit Microphone 1.0m Note: H= 0.5 × height of outdoor unit Noise level dB(A) Model OU-1403INV____ 62.5 OU-1603INV____ Outdoor Units...
Page 60
Electrical Control System Part 4 Electrical Control System 1. Electrical Control Function ..........2. Troubleshooting ..............3. Controller ................Electrical Control System...
Page 61
Electrical Control Function 1. Electrical Control Function 1.1 Definition T1: Indoor room temperature T2: Coil temperature of indoor heat exchanger middle. T2B: Coil temperature of indoor heat exchanger outlet. T3: Coil temperature of condenser T4: Outdoor ambient temperature T5: Compressor discharge temperature 1.2 Main Protection 1.2.1 Time delay at restart for compressor.
Page 62
Electrical Control Function 1.3 Operation Modes and Functions 1.3.1 Fan mode ( 1) Outdoor fan and compressor stop. (2) Temperature setting function is disabled, and no setting temperature is displayed. (3) Indoor fan can be set to high/med/low/auto. (4) The louver operates same as in cooling mode. (5) Auto fan: T1-24 High...
Page 63
Electrical Control Function For the others models: High low temperature cooling Outdoor fan in low temperature cooling mode acts as follow: Exit low temperature cooling mode High fan running for 1 minute 1.3.2.3 Indoor fan running rules In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and auto. The auto fan: High Medium...
Page 64
Electrical Control Function 1.3.2.1 Outdoor PMW open angle control The unit is working in heating mode with the EXV open 300P for 3 minutes, then adjusting PMW open angle according to the temperature of compressor discharge every 2 minutes. 1.3.3.2 Outdoor fan running rules: For OU-48 DC_FAN_SSLOW_SPD_ADD 21℃...
Page 65
Electrical Control Function Time1 3℃ Time2 Time conditions: time1 Time conditions(Meet the following conditions) 1.Running in heating mode 2. T4≥3 ℃ 3. Compressor is on 4. T3≤TempEnterDefrost_ADD ℃ Cleared conditions (Meet any one of the following conditions) 1. Compressor is off. 2.
Page 66
Electrical Control Function 4-Way valve no longer than 10min Compressor TimeA 10S 30S Indoor fan Outdoor fan PMV running 8 mins with 300P 480P Condition of ending defrosting: If any one of following items is satisfied, defrosting will stop and the machine will turn to normal heating mode.
Page 67
Electrical Control Function All protections are active and the same as that in cooling mode. 1.3.6 Timer function 1.3.6.1 Timing range is 24 hours. 1.3.6.2 Timer on. The machine will turn on automatically when reaching the setting time. 1.3.6.3 Timer off. The machine will turn off automatically when reaching the setting time. 1.3.6.4 Timer on/off.
Page 68
Electrical Control Function 1.3.10 Point Check Function There is a check switch in outdoor PCB. Press the switch SW1 to check the states of unit when the unit is running. Press the switch N times it will display the content corresponding to No. N. After getting into the check function, it will display No.
Page 69
Electrical Control Function Frequency limit Bit0 caused by voltage DC fan motor speed The display value is between 30~120 degree. If the temp. is lower than 30 degree, the digital display tube will show “30”.If the temp. is higher than 99 degree, the digital display tube will IGBT radiator temp.
Troubleshooting 2. Troubleshooting 2.1 Display board 2.1.1 Icon explanation on indoor display board (Big cassette). 2.1.2 Icon explanation on indoor display board (Ceiling & Floor) 2.1.3 Icon explanation on indoor display board (A5 Duct) PRE-DEF indicator(cooling and heating type) or fan only indicator(cooling only type) Alarm indicator Timer indicator Infrared signal receiver...
Page 71
Troubleshooting 2.1.5 Display board of GA floor standing 2.1.6 Display board of M floor- standing Electrical Control System...
Page 72
Troubleshooting 2.2 Indoor unit malfunction For floor standing: Contents Codes Evaporator low temp. protection Outdoor unit malfunction Indoor / outdoor units communication error Open or short circuit of T1 temperature sensor Open or short circuit of T2 temperature sensor Open or short circuit of T2B temperature sensor EEPROM chip malfunction Indoor fan speed is out of control For the others tyoes:...
Page 73
Troubleshooting 2.3 Outdoor unit malfunction Display Malfunction or Protection Outdoor EEPROM malfunction Indoor / outdoor units communication error Communication malfunction between IPM board and outdoor main board Open or short circuit of T3 or T4 temperature sensor Voltage protection of compressor PFC module protection (Only for 48K with 1 phase) Top temperature protection of compressor High pressure protection...
Page 74
Troubleshooting 2.4 Solving steps for typical malfunction 2.4.1 For the indoor unit 2.4.1.1 Open or short circuit of temperature sensor Check the connections between temperature Correct the connections. sensor and PCB. Are the connections good? Check the resistance value of the sensor via Appendix 1 Is it normal? Replace indoor or outdoor PCB.
Page 75
Troubleshooting 2.4.1.2. Outdoor unit malfunction Outdoor unit malfunction Whether the outdoor main board has error Refer to corresponding solving steps display Whether the outdoor Check whether the power is on unit is power on Check whether the communication wire Connect the wiring well or between the indoor and replace the communication wire outdoor unit is...
Page 76
Troubleshooting 2.4.1.3. Indoor EEPROM malfunction Shut off the power supply and turn it on 5 seconds later. Is it still displaying the error code? If the EEPROM chip is welded on PCB, replace the PCB directly. Otherwise, Insert the EEPROM well check whether the EEPROM chip plugged in PCB well?
Page 77
Troubleshooting 2.4.1.5. Indoor fan Speed has been out of control. Shut off the power supply and turn it on 1 minute later. Is it The unit operates normally. still displaying the error code? Shut off the power supply, Replace indoor fan rotate the fan by hand.
Page 78
Troubleshooting Control chip is in main PCB Orange Grey White Pink Black Color Signal Color Blue Yellow Signal 1) Release the UVW connector. Measure the resistance of U-V, U-W, V-W. If the resistance is not equal to each other, the fan motor must have problems and need to be replaced.
Page 79
Troubleshooting 2.4.2 For the super-slim cassette with up-down panel 2.4.2.1 Communication error between indoor unit and up-down panel 2.4.2.2 Up-down panel is defective Electrical Control System...
Page 80
Troubleshooting 2.4.2.3 Up-down panel is not closed Electrical Control System...
Page 81
Troubleshooting 2.4.3 For the outdoor unit 2.4.3.1. E0 malfunction E0 display Outdoor EEPROM malfunction If the EEPROM chip is welded on PCB, replace the PCB directly. Otherwise, Insert the EEPROM well check whether the EEPROM chip plugged in PCB well? Replace the outdoor main board Electrical Control System...
Page 82
Troubleshooting 2.4.3.2 . E2 malfunction E2 display Indoor / outdoor units communication error Power off, then turn on the unit 5 seconds later(reconnect the power wire).Is the error still displaying after several minutes? Check whether there’s any interference. Remove interference. Such as too many lamps, power Increase the capacity of anti- transformers? Or the signal wire...
Page 83
Troubleshooting 2.4.3.3. E3 malfunction E3 display Communication malfunction between IPM board and outdoor main board Is there at least one LED in the IPM board light? Check the signal wire between the IPM module and the main board, is it connected good? Reconnect and retry.
Page 84
Troubleshooting 2.4.3.4. E4 malfunction E4 display Judge 1: Outdoor condenser temp. sensor (T3) is malfunction Check whether the wiring of the condenser temp. sensor(T3) is Connect the wiring well broken off Check whether the resistance of condenser temp. sensorT3) is Replace condenser temp.
Page 85
Troubleshooting 2.4.3.5. E5 malfunction(For single phase units) E5 display Voltage protection Check the voltage of outdoor unit power supply, whether the voltage Check the power supply between L(1) and N is about 220~240VAC Replace the power board, then check whether the system can run normally Check whether the voltage of IPM board P and N is...
Page 86
Troubleshooting 2.4.3.6. E5 malfunction(For three phases units) E5 display Voltage protection Check the voltage of outdoor unit power supply, whether the voltage between L(1) Check the power supply ,L(2),L(3)and N is about 220VAC and between L(1) ,L(2),L(3) is about 380VAC Replace the power board, then check whether the system can run normally...
Page 87
Troubleshooting 2.4.3.7. E6 malfunction (Only for 48K with 1 phase) Electrical Control System...
Page 88
Troubleshooting 2.4.3.8. P0 malfunction Electrical Control System...
Page 89
Troubleshooting 2.4.3.9. P1 malfunction Electrical Control System...
Page 90
Troubleshooting 2.4.3.10. P2 malfunction Electrical Control System...
Page 91
Troubleshooting 2.4.3.11. P3 malfunction Electrical Control System...
Page 92
Troubleshooting 2.4.3.12. P4 malfunction When compressor discharge temperature is higher than 115°C, the unit will stop, and unit runs again when compressor discharge temperature is lower than 90°C. P4 display Temperature protection of compressor discharge Check whether the Check whether the compressor discharge temp.
Page 93
Troubleshooting 2.4.3.13. P5 malfunction When condenser high temp. is more than 65°C, the unit will stop, and unit runs again when outdoor pipe temp. less than 52°C. P5 display High temperature protection of condenser Replace the temperature sensor Check whether the condenser temperature is more than 65°C Check whether the...
Page 94
Troubleshooting 2.4.3.14. P6 malfunction (For single phase units) P6 display IPM module protection Check whether the voltage Check whether the Regulate it to correct, range of P-N on IPM input power supply is then check whether the correct? 220-240V, 1N, system can work module is normal? DC277-...
Page 95
Troubleshooting 2.4.3.15. P6 malfunction (For three phases units) P6 display IPM module protection Check whether the Regulate it to correct, Check whether the voltage input power supply is then check whether the range of P-N on IPM module is correct? 380-415V, 3N, system can work normal? DC 350-650V 50Hz...
Page 96
Troubleshooting 2.4.3.16. P7 malfunction P7 display High temperature protection of evaporator Whether the Whether compressor connection is Reconnect and retest operates? good? Check the Check whether the heat resistance value of exchanger is dirty, the air- the sensor via Replace the temperature sensor outlet is blocked and the Appendix 1,Is it indoor fan is running...
Page 97
Troubleshooting Appendix 1 Temperature Sensor Resistance Value Table ( ℃ --K) ℃ ℃ ℃ ℃ K Ohm K Ohm K Ohm K Ohm 12.6431 2.35774 0.62973 115.266 108.146 12.0561 2.27249 0.61148 101.517 11.5000 2.19073 0.59386 96.3423 10.9731 2.11241 0.57683 89.5865 10.4736 2.03732 0.56038...