Fig. 8: Power contact on left side
Possible damage of the device
Note that, for reasons of electromagnetic compatibility, the PE contacts are capacitatively coupled to the
mounting rail. This may lead to incorrect results during insulation testing or to damage on the terminal (e.g.
disruptive discharge to the PE line during insulation testing of a consumer with a nominal voltage of 230 V).
For insulation testing, disconnect the PE supply line at the Bus Coupler or the Power Feed Terminal! In or-
der to decouple further feed points for testing, these Power Feed Terminals can be released and pulled at
least 10 mm from the group of terminals.
Risk of electric shock!
The PE power contact must not be used for other potentials!
3.3
Disposal
Products marked with a crossed-out wheeled bin shall not be discarded
with the normal waste stream. The device is considered as waste
electrical and electronic equipment. The national regulations for the
disposal of waste electrical and electronic equipment must be observed.
KL31x2/KS31x2
NOTE
WARNING
Version: 2.6.0
Mounting and wiring