Page 1
NetSure™ 400V DC Power System User Manual Specification Number: 584001200 Model Number: 9500...
Page 2
The information contained in this document is subject to change without notice and may not be suitable for all applications. While every precaution has been taken to ensure the accuracy and completeness of this document, Vertiv assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
Vertiv™ NetSure™ 400V DC Power System User Manual TABLE OF CONTENTS Admonishments Used in this Document ..........................iv Important Safety Instructions ..............................v Safety Admonishments Definitions ............................................v Safety and Regulatory Statements ............................................v Déclarations de Sécurité et de Réglementation ......................................v 1 Customer Documentation Package ..........................1...
Vertiv™ NetSure™ 400V DC Power System User Manual Admonishments Used in this Document will likely DANGER! Warns of a hazard the reader be exposed to that will result in death or serious injury if not avoided. (ANSI, OSHA) could WARNING! Warns of a potential hazard the reader...
Vertiv™ NetSure™ 400V DC Power System User Manual Important Safety Instructions Safety Admonishments Definitions Definitions of the safety admonishments used in this document are listed under “Admonishments Used in this Document” on page iv. Safety and Regulatory Statements Refer to Section 4154 (provided with your customer documentation) for Safety and Regulatory Statements.
2 System Description 400V DC Output @ up to 600kW Power System The Vertiv™ NetSure™ 9500 400V DC Power System is a complete integrated power system containing rectifiers, intelligent control, metering, monitoring, and distribution. A system can consist of a Main Power Module/Bay, up to four (4) Expansion Power Modules/Bays, optional Distribution Modules/Bays, and Battery Cabinets.
Vertiv™ NetSure™ 400V DC Power System User Manual 2.1 Power Module/Bay (List 01, 03) A system can consist of a Main Power Module/Bay and up to four (4) Expansion Power Modules/Bays. These Power Modules/Bays are installed in a row next to each other. The system can be expanded either left or right of the Main Power Module/Bay (but not in both directions).
Vertiv Provided Battery Cabinet Vertiv offers a choice of battery models factory installed and connected in a cabinet (List 90, 91, 92, 93). Each Battery Cabinet houses one (1) 400V battery string consisting of twenty-eight (28) 12V battery blocks (336V nominal). Refer to the Battery Cabinet instructions (IM58400120090) for more information.
“Control Voltage Present” Indicator: Illuminates green to indicate the converter power supply in the Main Power Module/Bay is functioning. (If off when system is in operation, contact Vertiv Technical Support.) (The converter power supply provides 48V DC for controls.) “Ground/Insulation Fault Alarm”...
“Control Voltage Present” Indicator: Illuminates green to indicate the converter power supply in the Expansion Power Module/Bay is functioning. (If off when system is in operation, contact Vertiv Technical Support.) (The converter power supply provides 48V DC for controls.) 3.4 Distribution Panel Lockout/Tagout (LOTO)
Vertiv™ NetSure™ 400V DC Power System User Manual • Bus Voltage Imbalance: Bus to ground voltage imbalance. The voltage difference between the +Bus to ground and the – Bus to ground is more than the “Voltage Imbalance Alarm Limit” parameter set in the ACU+ controller. The default setting for this parameter is 84V.
Page 13
Vertiv™ NetSure™ 400V DC Power System User Manual Figure 3.1 Main Power Module/Bay Power and Control Section Controls and Indicators Output Control Voltage Voltage Ground/Insulation Present Present Fault Alarm Indicator Indicator Indicator Output Control Ground/Insulation Voltage Voltage Fault Present Present...
Page 14
Vertiv™ NetSure™ 400V DC Power System User Manual Figure 3.2 Expansion Power Module/Bay Power and Control Section Controls and Indicators Output Control Voltage Voltage Present Present Indicator Indicator Output Control Voltage Voltage Present Present Rectifier #2 Rectifier #1 Rectifier #4...
Vertiv™ NetSure™ 400V DC Power System User Manual 3.7 Adding a Circuit Breaker to a List 21HA Distribution Panel DANGER! Hazardous DC voltage (400V DC) is present. The distribution panel MUST be completely isolated from all power sources. Refer to Figure 5.1 as this procedure is being performed.
4.3 Recommended Battery Maintenance Refer also to the Battery Cabinet Installation and Operation Instructions (IM58400120090). Lockout/Tagout (LOTO) The “Battery Disconnect Circuit Breaker” on an Vertiv Battery Cabinet contains a bracket which allows the circuit breaker to be padlocked in the off position. Maintenance Inspect the batteries according to battery manufacturer’s instructions.
Vertiv™ NetSure™ 400V DC Power System User Manual 5 Troubleshooting and Repair 5.1 Important Safety Instructions DANGER! Adhere to the “Important Safety Instructions” presented at the front of this document. 5.2 Contact Information Refer to Section 4154 (provided with your customer documentation) for support contact information.
Vertiv™ NetSure™ 400V DC Power System User Manual With the Manual menu screen displayed, navigate to and select “Rectifier” (ENT) / “All Rect Ctrl” (ENT). Navigate to “Clear Comm Fail”. Press ENT. “Yes” highlights. Press ENT to select the operation. Press ENT again to confirm.
Page 19
Vertiv™ NetSure™ 400V DC Power System User Manual Replacing a Circuit Breaker in a List 21HA Distribution Panel DANGER! Hazardous DC voltage (400V DC) is present. The distribution panel MUST be completely isolated from all power sources. Replace distribution circuit breakers with the same type and rating. Refer to System Application Guide SAG584001200 for part numbers.
Page 20
Vertiv™ NetSure™ 400V DC Power System User Manual Figure 5.1 Adding or Replacing a DC Distribution Circuit Breaker in a List 21HA Distribution Panel to +200V DC Load to +200V DC Load Distribution Terminal Distribution Terminal to +200V DC to +200V DC...
Page 21
Vertiv™ NetSure™ 400V DC Power System User Manual Replacing an AC Input Surge Protector in a Power Module/Bay DANGER! Hazardous AC voltage (380V/400V/480V AC) is present behind the access covers being removed in this procedure. Disconnect AC input power from the Power Module/Bay. Follow local lockout/tagout procedures to ensure the external AC input circuit breaker remains in the OFF position during this procedure.
Page 22
Vertiv™ NetSure™ 400V DC Power System User Manual Figure 5.2 AC Input Surge Protector Replacement in a Power Module/Bay Power and Control Section AC Surge Protector Rear AC Surge Protector Plug-In Connector AC Surge Protector Terminal Block AC surge protector ground...
Need help?
Do you have a question about the NetSure 9500 and is the answer not in the manual?