TYPE C
COMMON VENTED FLUE SYSTEMS IN MULTI FLOOR BUILDINGS
43
This appliance can operate on a U-Duct common flue system. The maximum lengths for the interconnecting flue can be found in
Section 10.2.
Only use a C43 venting system when the common duct is a natural draught chimney. The
common duct is part of the building, not a part of the system.
Concrete components of the U-Duct must meet the requirements of BS EN 1858.
10.17.1
CONDENSATE DRAIN
Condensate can flow back to the appliance; this will travel through the heat exchanger into the condensate drain via the trap.If the
flue system rises at an angle of at least 3 (50mm per metre), no additional condensate drain will be required. Failure to provide an
adequate rise in the flue system may lead to pooling of condensate, which may lead to premature failure of the flue system.
Nominal Flue
Model No.
Diameter
EKW116CE
100+/-0.6
EKW146CE
150+/-0.6
150+/-0.6
EKW176CE
150+/-0.6
EKW206CE
150+/-0.6
EKW236CE
C
(TWIN PIPE) FLUE SYSTEMS
53
Flue system specifications
MANUFACTURER MUELINK AND GROL (M&G)
TEMPERATURE CLASS T120
FLUE GAS MATERIAL PP
Each Twin-Pipe starter assembly includes the items shown in the tables below
COMPONENTS INCLUDED
Item No.
M75257
AIR INLET TRANSITION Ø100mm ALU
M85189
SAMPLING POINT Ø100mm PP
TWIN-PIPE FLUE STARTER ASSEMBLY
The concentric flue assembly for models EKW146CE and EKW176CE consists of a twin-pipe flue system with a concentric
terminal- this system should be used if a twin-pipe assembly is required for these models.
See
C33 CONCENTRIC VERTICAL FLUE SYSTEMS
Mass Rate @ 100%
(@ 9% CO2) (G20)
42.5g/s
53.2g/s
63.9g/s
74.6g/s
85.2g/s
TABLE 8.6
Item No EKWTF002
TWIN-PIPE FLUE STARTER ASSEMBLY
Kit contains components to start the connection to the appliance only
MODELS EKW116CE
Description
MODELS EKW146CE,EKW176CE
Mass Rate @ 100%
Mass Rate @ 23%
(@ 10.5% CO2)
(@ 9% CO2) (G20)
(G31)
9.8g/s
44.2g/s
12.2 g/s
55.4g/s
14.7g/s
66.6g/s
17.1 g/s
77.6g/s
19.6g/s
88.8g/s
FLUE GAS MASS RATES
Mass Rate @ 23%
(@ 10.5% CO2)
(G31)
10.2g/s
12.7g/s
15.3g/s
17.9g/s
20.4g/s
Number
Quantity
1
1
2
1
38