Common Flue Cascading; Safety Measures Common Flue Systems - Lochinvar EFW 85 Installation, Commissioning, User And Maintenance Instructions

Wall mounted gas fired condensing water heater
Table of Contents

Advertisement

12 COMMON FLUE CASCADING

C10 Common flue gas systems.
WARNING:
If other than M&G flue gas materials are used, please contact your
boiler supplier.
If using C10 flue gas system for a so called "CLV" system the
following must be applied:
A data plate shall be present on the connection interface to the
common flue duct. It shall contain the following information:
a) the common duct system is for C(10) boilers;
b) the maximum allowable combustion products mass flow rate;
c) the dimensions of the connection to the common ducts;
d) a warning when the boiler is disconnected the air outlet and the combustion product inlet
openings shall be closed and checked on tightness.
e) the name of the manufacturer of the common flue duct or his identifying symbol.
C11 Common flue gas systems.
A special common flue gas calculation manual for C11 flue gas systems is available on request at your boiler sup-
plier.

Safety measures Common Flue Systems

In case EFW water heaters are installed with a common flue system and the combustion air is drawn directly
from the room, safety measures have to be taken.
Indicated hazard.
The EFW water heaters are equipped with a Non-return valve to prevent recirculation of flue gas of a running
heater through one or more heaters which are not running and are connected with a common flue system. This
Non-return valve might leak over time by pollution, incorrect maintenance or other unexpected cause. In case
the combustion air is drawn from the room, flue gas might enter the room, which could lead to Carbon Monoxide
(CO) poisoning.
Safety measures:
To cover this risk of Carbon Monoxide (CO) poisoning in combination with combustion air drawn directly from the
room, two safety measures have to be taken:
1. Guaranteed sufficient outside air supply for combustion and ventilation according local standards, codes
and regulations.
2. Use an CO detector for alarm and switching module to switch off all the heaters. The CO alarm system must
be according to national and local standards.
Additional Safety Advice
3. Use always the cascade manager of the heater and check if power mode 2 is switched on. Power mode 2 is
selected at parameter 148.
Combine all air intake terminals of the heaters, which do not necessarily have to be connected to the out-
4.
side.
Ad 1. Guaranteed sufficient outside air supply for combustion and ventilation according local standards, codes
and regulations.
The heater-room must have sufficient outside air supply for combustion and ventilation. There are many ways of
creating sufficient outside air supply, depending on location of the heater-room in the building. The demands for
the (size of the) heater-room and required ventilation is prescribed in local standards, codes and regulations.
The execution and size of the outside air supply must be engineered and calculated by engineers thoroughly fa-
miliar with all aspects of the subject.
The outside air supply must be guaranteed during the lifetime of the installation. Risks of blocking or reducing the
outside air supply, should be assessed and covered by the engineer in his / her design. Common obstacles in the
outside air supply are e.g. venting opening closed or reduced by pollution, a cupboard, a parked truck / car,
closed for heat loss arguments, etc., etc.
E93.1804.014
61

Advertisement

Table of Contents
loading

This manual is also suitable for:

Efw 105Efw 125Efw 155

Table of Contents