To install the flue connection to the EKW146CE-EKW176CE Water Heater the following procedure should be followed:
1.
Check you have all items shown in Section 10.9.1
2.
Check the flue temperature sensor (supplied with the Water Heater) is securely located into the hole on the exhaust
transition.
If the flue temperature sensor is not fitted, the flue gas may exceed the maximum temperature rating of the
flue and can lead to severe personal injury, death or substantial property damage.
3.
Insert the 90° elbow (Item 5) in to the exhaust transition ensuring the socket is pointing upwards.
4.
Insert the 100mm to 130mm expander (Item 4) in to the 90° elbow.
5.
Insert the 130mm to 150mm expander (Item 3) in to the 100mm to 130mm expander.
6.
Insert the air intake transition (Item 2) into the intake connection (Item 1) and tighten the worm drive clip.
The completed installation should look like the photos shown below
EXHAUST TRANSITION KIT FITTED EKW146CE-EKW176CE
10.9.3
TRANSITION KIT FITTED TO APPLIANCE
3
AIR INLET TRANSITION KIT FITTED EKW146CE-EKW176CE
5