Dhw Settings; Anti-Cycling - Lochinvar ECOKNIGHT EKW116CE Installation, Commissioning, Maintenance And User Instructions

Floor standing gas fired condensing circulating type water heater
Table of Contents

Advertisement

DHW SETTINGS

22.4.1
DHW TANK SET POINT
By installing a tank sensor, the SMART SYSTEM control can perform the tank thermostat function. The SMART SYSTEM control
automatically detects the presence of this sensor, and generates a DHW call for heat when the tank temperature drops below
the tank set point differential (Tank Set point Differential parameter), and finishes the call for heat when the tank temperature
reaches tank set point. This parameter can be changed by the installer by accessing the DHW Tank Set point parameter. The
temperature range of this parameter is from the tank minimum set point to the tank maximum set point. The default value is 49°C.
This should be set at 60°C.
The SMART SYSTEM control will only operate with the tank sensor fitted.
22.4.2
TANK SET POINT DIFFERENTIAL
When a tank sensor is installed, the tank temperature must drop this amount below the tank set point (DHW Tank Set point
parameter) before the water heater turns back on. The installer can adjust this setting by accessing the Tank Set point Differential
parameter. The minimum setting is 0°C, and the maximum is 22°C. The default setting is 3°C.
22.4.3
DHW RECIRCULATION PUMP OFFSET (RECIRCULATION PUMP)
The SMART SYSTEM control will turn the DHW recirculation pump on when the DHW return water temperature drops below the
DHW Tank Set Point minus the DHW Recirculation Pump Offset. The range for this parameter is 0° to 30°C. The default value is
5°C.
22.4.4
DHW RECIRCULATION PUMP DIFFERENTIAL
Once the SMART SYSTEM control turns the DHW recirculation pump on, the DHW return water temperature must increase by the
DHW Recirculation Pump Differential before the control turns the DHW recirculation pump back off. The range of this parameter is
0° to 50°C. The default value is 2°C.
22.4.5
TANK MINIMUM SET POINT
This setting controls the minimum tank set point for the tank temperature. The installer can adjust this by accessing the Tank
Minimum Set point parameter. The minimum setting is16°C and the maximum setting is the maximum tank set point (Tank
Maximum Set point parameter). The default value is 16°C.
22.4.6
TANK MAXIMUM SET POINT
This setting controls the maximum tank set point for the tank temperature. The installer can adjust this by accessing the Tank
Maximum Set point parameter. The minimum setting is the minimum tank set point (Tank Minimum Set point parameter) and the
maximum setting is 88°C. The default value is 88°C.

ANTI-CYCLING

22.5.1
ANTI-CYCLING TIME
Once the burner turns off, a set amount of time must elapse before the control will respond to a new demand. The control will
block the new heat demand and anti-cycling will be shown in the display until the time has elapsed or the water temperature drops
below the Anti-Cycling Override Differential parameter. This parameter can be changed by the installer by accessing the Anti-
Cycling Time parameter. The time range for this parameter is 1 minute to 10 minutes. The default value is 1 minute.
22.5.2
ANTI-CYCLING OVERRIDE DIFFERENTIAL
The control will bypass the anti-cycling time if the inlet water temperature drops too much. The control will use the inlet water
temperature present at the water heater when it shuts off as the starting point. If the inlet temperature drops below the
temperature parameter, the control will abort anti-cycling and allow the water heater to fire. This parameter can be changed by
the installer by accessing the Anti-Cycling Override Differential parameter. The temperature range of this parameter is 0°C to
30°C. The default value is 6°C.
87