To install the flue connection to the EKW116CE Water Heaters the following procedure should be followed:
1.
Check you have all items shown in Section 10.8.1
2.
Check the flue temperature sensor (supplied with the Water Heater) is securely located into the hole on the exhaust
transition.
If the flue temperature sensor is not fitted, the flue gas may exceed the maximum temperature rating of the
flue and can lead to severe personal injury, death or substantial property damage.
3.
Insert the air intake transition (Item 5) into the intake connection reducer and tighten the worm drive clip.
4.
To the bottom (exhaust) connection of the concentric adaptor fit one of the 80mm 90 elbows, then fit the 80mm x500mm
flue pipe cut to length as in Section 1.1.1.
5.
To the side (intake) connection of the concentric adaptor, fit the remaining 90 elbows.
6.
Fit the Concentric adapter (item 3) to the exhaust flue pipe and air inlet elbows
7.
Fit the flue gas test point (Item 2) and clamp using its locking band.
The completed transition kit should look like the photos shown below.
REAR VIEW TRANSITION KIT EKW116CE
10.8.3
TRANSITION KIT FITTED TO APPLIANCE
SIDE VIEW TRANSITION KIT EKW116CE
24