Parameters; Eetc 11, 12, 21 And 22; Assignment; Thermostat - Danfoss EET Series User Manual

Refrigeration controller
Table of Contents

Advertisement

Refrigeration controller, type EET series

Parameters

EETc 11, 12, 21 and 22

Assignment

Table 4: Assignment
Parameter name
Assignment
Sensor Type
S2 Configuration
Relay 2 Configuration
(applicable only for EETc 2x series)

Thermostat

Table 5: Thermostat
Parameter name
Thermostat
Lowest Temperature Limit (°C)
Highest Temperature Limit (°C)
Lowest Temperature Differential (K) Ldi
Highest Temperature Differential (K) Hdi
Initial pull down ON/OFF
Initial Pull down duration (Hrs)
Initial pull down initiate tempera-
ture (°C)

Compressor

Table 6: Compressor
Parameter name
Compressor
Min Run time (Sec.)
Min Stop time (Sec.)
© Danfoss | Climate Solutions | 2023.07
Default
Code
Min.
Max.
value
ASi
NTC10K
NTC5K
NTC10K
S2C
EuA
nC
dES
o2C
dEF
nC
Fan
Default
Code
Min.
Max.
value
THE
LSE
0
-100
120
HSE
10
-100
120
2
1
50
2
1
50
IPE
OFF
OFF
ON
IPD
0
0
120
Pit
50
-50
120
Default
Code
Min.
Max.
value
COP
Crt
0
0
1800
CSt
120
0
1800
Description
Sensor type (all sensors must be of same type)
NTC5K - NTC 5000 Ohm at 25 °C (Beta value=3980 @ 25/100 °C)
NTC10K - NTC 10000 Ohm at 25 °C (Beta Value 3980 @ 25/100 °C)
Desired configuration for S2 port
nC - Not used/configured
Con - Condenser Sensor
EuA - Defrost/evaporator Sensor
doC - Door Sensor (Normally closed type)
doo - Door Sensor (Normally open type)
ESP - Eco Switch - Push button type
ESt - ECO Switch - Toggle type
dES - Defrost switch - Push Button type only
Desired configuration for relay 2
nC - Not Connected
dEF - Configured for defrost heater or defrost valve
Fan - Configured for evaporator fan
Description
Cut-out temperature at coldest position of the spindle (thermostat knob)
Cut-out temperature at warmest position of the spindle (thermostat knob)
The difference between the cut-out and the cut-in at coldest position of the ther-
mostat.
The difference between the cut-out and the cut-in at warmest position of the ther-
mostat.
Initial Pull down
OFF - Disable
ON - Enable
Initial Pull Down (IPD) provides faster cooling when the cabinet is powered up with
warmer inside temperature. During IPD, defrost will be skipped until the cabinet air
temperature reaches the cut-out temperature or the IPD duration expires. IPD oper-
ates only during power-up and can be enabled/disabled using this parameter.
Maximum time initial pull down can run. Initial pull down will terminate as soon as
this time expires regardless of the cabinet air temperature
It indicates the temperature at which initial pull down will be initiated.
• At Power-up: If the cabinet air temp. > Pit for more than 5 minutes, this will trig-
ger the Initial pull down.
Description
To prevent the compressor from frequent cut-outs, it ensures that the compressor
runs for at least the specified time. It overrides the cut-out temperature. (Tip: Setting
it too high could lead to unneccessary deep temperatures)
To prevent the compressor from frequent cut-ins, the parameter ensures that the
compressor remains off for at least the specified time under this parameter. It over-
rides the cut-in temperatures. (Tip: Setting it too high could lead to unneccessary
warm temperatures)