Example: Check IO configuration

Wizard assignment of inputs and outputs (I/0)

Once the wizard is applied, the IO functions are automatically
assigned to hardware inputs and outputs�
The screens below shows how the IO functions are assigned
according to the example�
Main menu
Digital outputs

Assignment of inputs and outputs

The table indicates rules for assignment of inputs and outputs via the wizard�
Digital outputs (DO1-DO8)
PWM outputs for capacity
control of Digital scroll or
Stream 4 compressor are placed
on the solid state relays DO5
and DO6
Starting from DO1:
Compressor start relays
followed by unloading valves
for respectively suction group
A and B
Condenser fan
Injection ON for A/B *
Alarm relay
* Special features to be enabled through configuration screens. Not part of the wizard setup.
14
Press ENTER to select
I/O configuration
IO configuration menu
Digital inputs
Digital inputs (DI1-DI8)
Compressor safety inputs for
respectively suction group A
and B
Fan safety inputs
External Main switch (ON/
OFF) *
HP safety switch*
LP safety switch *
Night setback *
Heat recovery *
Load shedding *
General alarm inputs 1-3 *
Technical brochure RC8CF102 © Danfoss 08-2014
Press ENTER to select
digital and analog I/O
Analog outputs
Analog outputs (AO3 – AO4)
Speed control of compressor
for respectively suction group A
and B
Speed control of condenser
Analog inputs
Analog inputs(AI1-AI8)
PoA og PoB suctionpressure are
placed on AI1 and AI2
Pc condensing pressure is
placed on AI3
Sc3 outdoor temperature is
placed on AI4
S4A and S4B suction media
temperature sensors *
S7 condenser media
temperature sensor *
Sd komp� 1 discharge temp�
sensor for digital scroll/Stream
compressor for suction A and B
Ss suction gas temperature for
suction group A and B *
Sd discharge temperature for
suction A and B *
Saux for general thermostat *