Adjusting Settings in Configuration Mode

Settings

Setting Name
Inverter Ignition Control
LBCO Voltage
LBCO Shutdown Delay
Timer
LBCO Recovery Voltage
52
Setting
Default
Range of
Number
Value
OFF
01
OFF
LOT
ATO
02
10.5
10.0 to 12.8
03
300
1 to 300
12.0 to 16.0
04
13.1
and OFF
Values
See Description of Ignition Control Features on page 37.
The voltage setting value can be adjusted by 0.1 increments. The
inverter is able to recover automatically at LBCO voltage +
0.2 volts.
When the range is from 1 to 20, the timer setting value can be
adjusted by 1-second increments. When the range is from 20 to
300, the timer setting value can be adjusted by 10-second
increments.
The range is from LBCO voltage + 0.2 to 16, adjusted by 0.1
increments. Selecting OFF or a higher value than the battery's
actual fully-charged voltage level will disable the auto-recovery
feature. You may manually reset the inverter/charger when the low
battery cut off event occurs.