8 MAINTENANCE

8.11
Routine maintenance & service checks:
Every 6 & 12 months (see service log sheets below) the Flowpress Mini should be inspected
for:-
Damage to the electrical supply cable.
Damage to the outlet flexible hoses.
Leakage from the Flowpress Mini or the connecting pipework.
Test unit operation
Float valve check
Water condition check
Expansion vessel pre-charge check
There are no user servicable wiring or components inside the controller
assembly. DO NOT remove the retaining screws or the membrane cover over
the display.
8.13 Spares
The Flowpress Mini is designed and built to be a reliable and high quality product, in the event of
spares being required please phone the Flowtech Water Solutions service team on 0333 200 1813.
8.14 Long term isolation and restart procedure
If the system is to be shut down for an extended period of time due to maintainance or system
modifications being carried out to the system the following steps must be taken.
1. Isolate mains inlet water from the Flowpress Mini.
2. Isolate the Flowpress Mini from the system and vent excess pressure to drain.
3. Run the Flowpress Mini to pump excess water from the tank to drain.
4. Isolate the electrical supply from the Flowpress Mini.
5. Ensure the Flowpress Mini cannot freeze. Damage will occure to the pumps if this is allowed to
happen.
6. Cover with plastic sheet or cardboard if work is to be conducted close to the Flowpress Mini.
flowpress
Mini Digital Pressurisation Unit

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Flowpress Mini Single and is the answer not in the manual?

This manual is also suitable for:

Flowpress mini twin

Table of Contents