8.15 Restart
To ensure the Flowpress Mini is in good working order after a prolonged period of maintainance the
following steps should be taken.
1. Inspect the Flowpress Mini for signs of damage.
2. Check Flowpress Mini tank for debris, remove debris and clean tank if needed. Debris may cause
damage to the pumps if it is allowed to be drawn in.
3. Check pressure vessel pre charge pressures before the system pressure is increased.
4. Open the mains water isolating valve allowing the Flowpress Mini tank to fill, and ensure the fill
valve is operating correctly and maintaining the correct water level.
5. Check for signs of leakage.
6. Open the drain valve on the outlet of the Flowpress Mini.
7. Turn on the mains electrical power and ensure both (if fitted) pumps can run (use test pump
option P6 if needed) and are pumping water to drain.
8. Close the drain valve and allow the Flowpress Mini to build pressure; the Flowpress Mini should
turn off as the isolation valve to the system is closed.
9. Open the Flowpress Mini outlet isolation valve and monitor the Flowpress Mini to ensure there is
no leaks as the system pressure increases.
10. Check all the pre set values on the Flowpress Mini, to ensure they are still suitable for the system
(after maintainance/modification)

9 ENVIRONMENT PROTECTION

Your appliance contains valuable materials which can be recovered or recycled. At the end of the
products' useful life, please leave it at an appropriate local civic waste collection point.