Programming manual
Printer Type : NONE
Printer Type : on RS232
BAUD RATE: 9600
Parity:E
StopBit:1
Print event from:
No printer
The control panel will save events to the events log but will be unable to provide a printout of
the events,
On RS232
The control panel will printout the events on the printer connected to the motherboard (refer
port
to the installation manual paragraph 4.2 - The motherboard) in accordance with the specified
priority (level of importance). The system structure in the SmartLeague application will show a
printer on the RS232 port.
Print event
from
Baud Rate
Num. bit
Parity
Stop bit
Flow C.
Panel printer
Only for "/P" models with housing for an on-board thermal printer (accessory item). The
control panel will printout the events on the thermal printer in accordance with the specified
priority (level of importance).
Print event
from
Log on Serial
The control panel will send the events in coded form to the RS232 port on the motherboard.
The event data can be sent to a home-automation system or saved to the SmartLAN board for
storage and retrieval via the Web Server.
Contact your service centre for details regarding event coding.
9.11 Closing the programming session
Press Esc until you return to the standby screen, the control panel will be "In service" (operating).
Remove the jumper (refer to paragraph 4.2 - [N] in the installation manual) to stop access to the
programming phase via control panel or computer.
Double check the functionality of all the input devices.
Programming the system
Num. Bit :8
Flow C.: XON/XOFF
ALL EVENTS
The control panel will print its own events and those received from other
control panels in accordance with the specified priority.
Printer speed (bps)
Number of data bits per packets
N=no parity bit, E=Even O=Odd
Number of Stop bits
Flow control type (XON/XOFF or NO)
As above.
Press keys W and X on the first line to select
the type of output for the events.
Press Esc to confirm the operation and step
back to the previous menu.
If you select the "RS232 Printer Type" option,
the communication protocol parameters will
appear:
Use keys S and T
to scroll the parameters
list.
Use keys W and X to select the values.
Press
to confirm and step back to the
previous menu.
Press Esc to cancel the changes and step
back to the previous menu.