  • Page 1 HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL SMARTGEN (ZHENGZHOU) TECHNOLOGY CO., LTD.
  • Page 2 Smartgen Technology at the address above. Any reference to trademarked product names used within this publication is owned by their respective companies. Smartgen Technology reserves the right to change the contents of this document without prior notice. Table 1 Software Version Date...
  • Page 3: Table Of Contents

    HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL CONTENT OVERVIEW ............................4 MODEL FUNCTION COMPARISON ....................4 PERFORMANCE AND CHARACTERISTICS ..................5 SPECIFICATION..........................6 MEASURED AND DISPLAYED DATA ....................7 OPERATING ............................8 OPERATION PANEL ........................8 INDICATOR DESCRIPTION ......................9 KEY FUNCTION DESCRIPTION ....................
  • Page 4: Overview

    It is the ideal product for dual power transfer. HAT552 is applicable for non-breaking switches, while HAT553 is applicable for non-breaking, one-breaking, and two-breaking switches.
  • Page 5: Performance And Characteristics

    HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL PERFORMANCE AND CHARACTERISTICS — System type can be set to: Mains - Generator, Generator - Mains, Mains - Mains; — 132x64 LCD with backlight, optional Chinese and English display, push-button operation; — Measure and display 2-channel 3 phase voltage, frequency and phase sequence;...
  • Page 6: Specification

    Active when ASW1 and ASW2 short connected; Active when BSW1 and Digital Close Input BSW2 short connected; Forced to Open Input GND connected is active (not available for HAT552); Digital Input 1 GND connected is active. 1. 1 RS485 isolated port, MODBUS Protocol;...
  • Page 7: Measured And Displayed Data

    HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL MEASURED AND DISPLAYED DATA Table 4 Display Parameters Measured and Displayed Data Items A/B power phase voltage A/B power line voltage A/B power voltage phase sequence A/B power frequency Present continuous supply time...
  • Page 8: Operating

    HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL OPERATING OPERATION PANEL Fig. 1 HAT552 Front Panel Fig. 2 HAT553 Front Panel HAT552/HAT553 ATS Controller 2020-05-14 Version 1.1 Page 8 of 35...
  • Page 9: Indicator Description

    HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL INDICATOR DESCRIPTION Table 5 Indicator Description Indicator Name Indicator Description Alarm Indicator Slow flashing for warning alarms ( 1time per second); Fast flashing for fault alarms ( 5 times per second) Auto Mode Indicator Light on when current is Auto mode;...
  • Page 10: Lcd Display

    HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL LCD DISPLAY MAIN SCREEN Table 7 Main Screen Display Item Display Contents Home Page A power status, B power status, Generator start status, switch status; A/B power voltage and frequency; Power A power line voltage, phase voltage, phase sequence, frequency;...
  • Page 11: Status Description

    HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL STATUS DESCRIPTION Table 9 A Power Voltage Status Item Description A Available Delay for A power available detection A Unavailable Delay for A power unavailable detection Power Normal Power value is within normal range.
  • Page 12 HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL Table 12 Switch Status Item Description Ready to Transfer Enter switch transfer procedure Closing A A power is experiencing close delay. Opening A A power is experiencing open delay (HAT553). Closing B B power is experiencing close delay.
  • Page 13: Main Menu

    HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL When reminder information is active, it displays for 2s and then it disappears. Table 15 Reminder Information Item Description Press Reset Alarm The reminder for manual transfer to auto mode before alarm clear as fault alarm occurs.
  • Page 14: Genset Start/Stop Operations

    HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL GENSET START/STOP OPERATIONS MANUAL START/STOP 8.1.1 PANEL START/STOP In main screen, press Set/Confirm key to enter main menu interface; select "5. Test Genset" to enter manual start operation screen. When system type is "A Mains B Gen, A Gen B Mains, A Mains B Mains", the below operation interface is directly entered.
  • Page 15: Parameter Configuration

    HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL PARAMETER CONFIGURATION ILLUSTRATION In the first page of the main screen, press key to enter menu screen; select "Parameters Set" and press Confirm key to confirm and enter parameter setting password check interface. Input correct password and it will enter parameter main interface.
  • Page 16 HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL Item Range Default Description Lower limit return value; normal when it is above 14 Under Volt Return (0~200)% return value. 15 Rated Frequency (10.0~75.0)Hz 50.0 Rated frequency value for AC system 0: Disable 16 Over Freq.
  • Page 17 HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL Item Range Default Description 1: Fault 0: Auto Trans/Non Restore 8 Auto Trans/Restore (0-1) 1: Auto Trans/Restore 0: Inactive 9 Each Backup (0-1) 1: Active 0: Disable 10 Open Input Enable (0~1) 1: Enable (HAT553) If this is not connected, please set it to Disable.
  • Page 18 HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL Item Range Default Description Programmable Output Setting Relay Output 1 Active 0: Output(N/O) (0~1) Type 1: Output (N/C) 2 Relay Output 1 (0~36) Common Alarm Module Setting 0: Previous Mode 1 Power On Mode...
  • Page 19: Digital Input/Output Function Description

    HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL DIGITAL INPUT/OUTPUT FUNCTION DESCRIPTION 9.3.1 INPUT PORT FUNCTION DESCRIPTION Table 18 Input Port Function Description Item Description Not used Invalid Reserved Remote Gen On Load Genset start outputs; when Mains is normal, gen closes.
  • Page 20 HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL Item Description Reserved Relay outputs when switch close/open transfers; it stops outputting Transition Output when transfer is over; shortest output time is 1s. A&B Abnormal Output when A and B both are abnormal.
  • Page 21: Event Log

    HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL 10 EVENT LOG In the first page of the main interface, press key, and enter menu page. Select "Event Log", and then select to confirm. In this way Event Log interface is entered.
  • Page 22: Switch Operation Running

    (HAT553). Press auto key , auto status indicator is illuminated; Controller is in auto status (HAT552). In auto mode, controller will transfer switch based on the status of A power and B power, transfer priority and auto trans./restore status to ensure supply for load. The following illustrates control logics by the example of "A power master"...
  • Page 23 HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL 11.2.1 AUTO TRANS./RESTORE When Auto Trans./Restore is set, A power is master; if A power is normal, then A power closes; if A power is abnormal, B power is normal, then A power opens, B power closes; if A power recovers normal, then B power opens, A power closes.
  • Page 24 HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL 11.2.2 AUTO TRANS./NON RESTORE (ACTIVE FOR MUTUAL BACKUP) When Auto Trans./Non Restore is set, and Mutual Backup is active, A power is master. If A power is normal, then A power closes; if A power is abnormal, B power is normal, then A power opens, and B power closes;...
  • Page 25 HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL 11.2.3 AUTO TRANS./NON RESTORE (ACTIVE FOR MUTUAL BACKUP) When Auto Trans./Non Restore is set, and Mutual Backup is inactive, A power is master. If A power is normal, and A power closes, when A power is abnormal, B power is normal, then A power opens, B power closes;...
  • Page 26: Auxiliary Contact Feedback Input Of Switch Open

    HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL 11.3 AUXILIARY CONTACT FEEDBACK INPUT OF SWITCH OPEN If switch needs to access to open feedback input, please firstly set open input enabled. Detailed setting method: in parameter setting interface enter "switch setting" interface, find "open input enable" and set it enabled;...
  • Page 27: Definition Of Connecting Terminals

    HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL 13 DEFINITION OF CONNECTING TERMINALS 13.1 DESCRIPTION OF CONNECTING TERMINALS Fig. 7 Controller Back Panel HAT552/HAT553 ATS Controller 2020-05-14 Version 1.1 Page 27 of 35...
  • Page 28 HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL Table 22 Terminal Function Description Functions Description Remark B disconnects output N Output AC power; control B power switch to disconnect, rated 8A. B disconnects output L A disconnects output N Output AC power; control A power switch to A disconnects output L disconnect, rated 8A.
  • Page 29: Description Of Controller Supply

    HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL 13.2 DESCRIPTION OF CONTROLLER SUPPLY Controller is AC supplied by the two AC sampling terminals directly. Fig. 8 AC Supply Diagram 13.3 DESCRIPTION OF RS485 CONNECTION Connecting of RS485 and Adapter is like below: Fig.
  • Page 30: Typical Wiring Diagram

    14 TYPICAL WIRING DIAGRAM Fig. 10 SGQ-N/T Application Diagram Table 23 Related Settings A Part of Parameter Setting Switch Type Setting No breaking (available for HAT553; not available for HAT552) HAT552/HAT553 ATS Controller 2020-05-14 Version 1.1 Page 30 of 35...
  • Page 31 HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL Fig. 11 FEITENG Application Diagram Table 24 Related Settings A Part of Parameter Setting Switch Type Setting Two breakings (HAT553) HAT552/HAT553 ATS Controller 2020-05-14 Version 1.1 Page 31 of 35...
  • Page 32 HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL Fig. 12 Connector Application Diagram Table 25 Related Settings A Part of Parameter Setting Switch Type Setting Two breakings (HAT553) Close Time Set it to 0 (HAT553) Switch Transfer Interval 10s (HAT553, set it according to factual occasions)
  • Page 33 Attached illustration for LO, NO connection inside controller: HAT553/HAT552 controller has automatic transfer function of ATS power supply inside. Only if one voltage of A power and B power is normal, by transfer between N/O contact and N/C contact of intermediate relay 1 and intermediate relay 2 ensure ATS power supply normal.
  • Page 34: Installation

    HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL 15 INSTALLATION The controller is designed by panel installation method, and is fixed by clips for installation. Unit: mm Fig. 15 Overall Dimensions and Cutout HAT552/HAT553 ATS Controller 2020-05-14 Version 1.1 Page 34 of 35...
  • Page 35: Fault Finding

    HAT552/HAT553 DUAL POWER ATS CONTROLLER USER MANUAL 16 FAULT FINDING Table 27 Fault Finding Symptom Possible Solutions Check DC supply voltage; Controller no response with Check DC fuse; power Check AC power; Check whether RS485 positive and negative are correctly connected;...