I/O Allocation to CompoBus/S Slaves

The CompoBus/S input area (IR 020 to IR 027) and CompoBus/S output area
(IR 030 to IR 037) are allocated for the CompoBus/S Terminal's I/O. The fol-
lowing table shows the I/O allocation of the CompoBus/S Terminal (IN0 to
IN15 and OUT0 to OUT15.)
Input area
Output area
Note
1. IN0 to IN15 are node numbers of Input Terminals and OUT0 to OUT15 are
node numbers of Output Terminals.
2. When the maximum number of CompoBus/S nodes is set to 16, IN8 to
IN15 and OUT8 to OUT15 can be used as work bits.
3. CompoBus/S Terminals with 8 points or less are allocated I/O bits in byte
units beginning from bit 00 or bit 08.
4. Only even addresses can be specified for 16-point CompoBus/S Termi-
nals.
I/O
IR word
15 14 13 12 11 10 9 8
020
021
022
023
024
025
026
027
030
031
032
033
034
035
036
037
Section 4-3
Bit address
Bit number
7 6 5 4
IN1
IN0
IN3
IN2
IN5
IN4
IN7
IN6
IN9
IN8
IN11
IN10
IN13
IN12
IN15
IN14
OUT1
OUT0
OUT3
OUT2
OUT5
OUT4
OUT7
OUT6
OUT9
OUT8
OUT11
OUT10
OUT13
OUT12
OUT15
OUT14