Wiring and Connections
CompoBus/S Terminals
Maximum Transmission
Line Length
Item
Trunk line length
Branch line length
Total branch line length 50 m max.
52
Downloaded from
Elcodis.com
electronic components distributor
3. Insert the pin terminals into the CompoBus/S terminal block on the
CPM2B-S CPU Board and tighten the locking screw.
The CompoBus/S Terminal specifications are as follows:
Tighten the terminal set screws to a torque of 0.2 to 0.4 N•m.
Note Before inserting the signal wires, loosen the terminal set screws sufficiently. If
the set screws aren't loosened, it won't be possible to insert the wires fully
and the wires won't be secured in the terminals.
The maximum lengths of the trunk line, branch lines, and total transmission
line length depend on the communications mode and the kind of transmission
line (flat cable or VCTF cable) being used. The maximum lengths are further
restricted if flat cable is being used with more than 16 Slaves.
Master
Branch
Slave Slave
line length
Slave Slave
Total branch line length = L
1
Max. length in high-speed mode
VCTF cable
Flat cable or 4-core VCTF cable
Up to 16 Slaves
100 m max.
100 m max.
3 m max.
3 m max.
50 m max.
b) We recommend the following crimper:
Weidmüller PZ1.5 Crimper (part number 900599)
c) The Weidmüller 901851 Sleeve cannot be used.
BDL
Trunk line length
Slave
Slave
+ L
+ L
+ L
+ L
2
3
4
5
17 to 32 Slaves
30 m max.
3 m max.
30 m max.
Section 3-5
BDH
Terminator
Slave
Max. length in long-distance mode
VCTF cable
Flat cable or 4-core
VCTF cable
500 m max.
Free branching
Total wire length:
6 m max.
200 m max.
120 m max.