Setting the Node Number

Set the DeviceNet node number with the rotary switches on the CPM2B-S
CPU Board. The allowed setting range is 00 to 63; node number settings 64 to
99 are not allowed. The rotary switch settings are read when the Unit's power
is turned ON.

Setting the Communications Speed

Set the DeviceNet communications speed with DIP switch 2 on the front of the
Unit. The DIP switch settings are read when the Unit's power is turned ON.
DIP switch 2 settings
Pin 1
OFF
ON
OFF
ON

Attaching Status Information

It is possible to enable and disable the attachment of the CPM2B-S status
information in transmissions from the CPM2B-S to the Master Unit.
The status attachment is set in DM 6605 of the PC Setup, as shown in the fol-
lowing table. The initial setting is 0 (attach status information); change this
setting to 1 to disable attachment of status information. Refer to 7-4 Status
Information for details on the status information.
Word
DM 6605
Allocate the DeviceNet read and write areas to specify what part of the PC's
data area will be used to read and write data from the DeviceNet Master Unit.
Specify the PC data area, starting word address, and number of bytes. Up to
64 bytes can be allocated for DeviceNet remote I/O.
Switch the CPM2B-S to PROGRAM mode and use a Programming Device,
such as a Programming Console or Support Software, to make the following
settings in DM 6605 to DM 6609 of the PC Setup. The settings in these words
are read only when the CPM2B-S is turned ON, so the PC's power must be
turned OFF and then ON again to make changes effective.
X10
DeviceNet
communications speed
Pin 2
OFF
125 kbps
OFF
250 kbps
ON
500 kbps
ON
Not used.
Bits
Function
04 to 07
Sets whether CPM2B-S status is transmitted to
the DeviceNet Master.
0 (Hex): Attach status ahead of data.
1 (Hex): Do not attach status ahead of data.
Section 7-1
X1
ON
Maximum total
communications distance
500 m max.
250 m max.
100 m max.
---
0
(Attach
status.)
Default