UPS5000-A-(400 kVA-600 kVA)
User Manual (60 kVA, PF=0.9)
Step 2 Click the Advanced tab, check that Use TLS 1.0 and Use TLS 1.1 are selected, and
then click OK.
Step 3 In the address box of the browser, enter https://
Step 4 Enter the correct user name and password and click Login.
Step 5 On the home page of the WebUI, choose Monitoring > UPS System > Running
Control, click Inv. ON, and confirm the operation to start the inverter.
Figure 4-2 Starting the inverter
----End
Starting the Inverter on the Old WebUI
Step 1 Open a browser (for example: Internet Explorer 11) and choose Tools > Internet
Options.
Step 2 Click the Advanced tab, check that Use TLS 1.0 and Use TLS 1.1 are selected, and
then click OK.
Step 3 In the address box of the browser, enter https://
Step 4 Enter the correct user name and password and click Login.
Step 5 On the WebUI, choose Monitoring > Control, click Inv. ON, and confirm the
operation to start the inverter.
Figure 4-3 Starting the inverter
Issue 06 (2022-01-27)
NO TE
If the power unit receives a startup command when it cannot be started, the startup
command will be kept for 1 minute. If the startup command is not cleared within 1 minute
(for example, other faults occur on the unit, or you perform shutdown or rectify faults) and
the unit can be started, the unit responds to the startup command.
Copyright © Huawei Technologies Co., Ltd.
UPS IP address .
UPS IP address .
4 Operations
90