UPS5000-A-(400 kVA-600 kVA)
User Manual (60 kVA, PF=0.9)
4.6.1 Forced Equalized Charging Test
Context
Before a forced equalized charging test, ensure that:
● The mains input is normal.
● Batteries are properly connected.
● Batteries are not in the equalized charging state.
Procedure
Step 1 On the home screen of the LCD, choose System Info > Maintenance > Battery
Maint.
Step 2 Tap Start next to Forced Equalized Charging to start a forced equalized charging
test.
Figure 4-9 Starting a forced equalized charging test
----End
Issue 06 (2022-01-27)
NO TICE
NO TE
The forced equalized charging test automatically stops in any of the following cases:
● The forced equalized charging test duration reaches the forced equalized charging
protection time (12–24 h, 18 h by default).
● The UPS generates a battery overtemperature, overvoltage, or overcurrent alarm.
● A fault alarm is generated.
Copyright © Huawei Technologies Co., Ltd.
4 Operations
96