UPS5000-A-(400 kVA-600 kVA)
User Manual (60 kVA, PF=0.9)
Table 7-1 Physical specifications
Item
Cabling
IP rating
Dimensions (H x
W x D)
Communication
Weight
Table 7-2 Internal switch specifications
UPS
UPS5000-
A-400K-FTS
UPS5000-
A-500K-FTS
UPS5000-
A-600K-FTS
Issue 06 (2022-01-27)
7

Technical Specifications

400 kVA
Routed in and out from the top or bottom
IP20 (IP21 can be reached by configuring an IP21
component.)
2000 mm x 1200 mm x 850 mm
Supports dry contacts, RS485 ports, and FE ports. Supports
the Simple Network Management Protocol (SNMP).
676 kg
Maintenance
Bypass
Switch
1000 V
AC/630 A/3P
1000 V
AC/800 A/3P
1000 V AC/
1000 A/3P
Copyright © Huawei Technologies Co., Ltd.
500 kVA
746 kg
Mains Input
Bypass Input
Switch
Switch
1000 V
1000 V
AC/800 A/3P
AC/630 A/3P
1000 V AC/
1000 V
1000 A/3P
AC/800 A/3P
1000 V AC/
1000 V AC/
1250 A/3P
1000 A/3P
7 Technical Specifications
600 kVA
2000 mm x 1400
mm x 850 mm
1030 kg
Output
Switch
1000 V
AC/630 A/3P
1000 V
AC/800 A/3P
1000 V AC/
1000 A/3P
114