UPS5000-A-(400 kVA-600 kVA)
User Manual (60 kVA, PF=0.9)
Item
Table 7-5 Mains input electrical specifications
Item
Input
system
Rated input
voltage
Input
voltage
range
Rated
frequency
Input
frequency
range
Input power
factor
THDi
Table 7-6 Bypass input specifications
Item
Input
system
Rated input
voltage
Rated
frequency
Issue 06 (2022-01-27)
Specifications
Voltage dip and temporary
interruption
Specifications
Three-phase, four-wire, and PE
380 V AC/400 V AC/415 V AC (line voltage)
● 80–280 V AC (phase voltage)
● 30°C < Ambient temperature ≤ 40°C: The UPS supports full
load when the voltage range is 198–280 V AC. The load is
derated to 35% when the voltage range is 80–198 V AC.
● 0°C ≤ Ambient temperature ≤ 30°C: The UPS supports full load
when the voltage range is 187–280 V AC. The load is derated
to 35% when the voltage range is 80–187 V AC.
50/60 Hz
40–70 Hz
● > 0.99 (full load)
● > 0.98 (half load)
● THDi < 3% (full linear load)
● THDi < 5% (full non-linear load)
Specifications
Three-phase, four-wire, and PE
380 V AC/400 V AC/415 V AC (line voltage)
50/60 Hz
Copyright © Huawei Technologies Co., Ltd.
7 Technical Specifications
IEC 61000-4-11