UPS5000-A-(400 kVA-600 kVA)
User Manual (60 kVA, PF=0.9)
Item
Recommended
cross-sectional
area (mm
Output
Output current (A)
Recommended
cross-sectional
area (mm
Battery
Nominal battery
input
discharge current (A)
Maximum battery
discharge current (A)
Recommended
cross-sectional
area (mm
Issue 06 (2022-01-27)
400 kVA
L1
2 x (4 x 185)
L2
2
)
L3
N
PE
185
608
U
2 x (4 x 185)
V
2
)
W
N
PE
185
789
945
+
2 x (3 x 185)
N
2
)
-
PE
185
When selecting, connecting, and routing cables, follow local safety regulations
and rules.
Select cables based on the maximum current under extreme working
conditions (such as low voltage and overload).
When the external conditions such as cable routing or ambient temperature
change, perform verification in accordance with the IEC 60364-5-52 or local
regulations.
If the rated voltage is 400 V, multiply the currents by 0.95. If the rated voltage
is 415 V, multiply the currents by 0.92.
When the primary loads are non-linear loads, increase the cross-sectional
areas of the neutral wires by 1.5–1.7 times.
The nominal battery discharge current refers to the current of forty 12 V
batteries at 480 V in standard configuration.
The maximum battery discharge current refers to the current when forty 12 V
batteries in standard configuration, that is, two hundred and forty 2 V battery
cells (1.67 V/cell), stop discharging.
Copyright © Huawei Technologies Co., Ltd.
500 kVA
3 x (4 x 185)
240
760
3 x (4 x 185)
240
987
1182
3 x (3 x 150)
240
3 Installation
600 kVA
3 x (4 x 240)
240
912
3 x (4 x 240)
240
1184
1418
3 x (3 x 240)
240