Technical Specifications; Standard Accessories - baltur TBL 1200 ME Instruction Manual For Installation, Use And Maintenance

Electronic modulation light oil burners
Table of Contents

Advertisement

Available languages

Available languages

TECHNICAL SPECIFICATIONS

MODEL
Minimum flow rate
Maximum flow rate
Minimum thermal power
Maximum thermal power
³) emissions
Viscosity
Operation
50hz transformer
50hz fan motor
50hz pump motor
50Hz three-phase electrical data
50Hz single-phase electrical data
Protection rating
Control box
Flame detection
Air flow rate regulation
Operating ambient air temperature
Sound pressure**
Weight with packaging
Weight without packaging
Calorific power below reference conditions 15° C, 1013 hPa (mbar):
Diesel fuel: Hi = 11.86 kWh/kg = 42.70 Mj/kg
The measurements have been carried out in accordance with EN 15036 - 1 standard.
** The acoustic pressure measured with burner operating at maximum rated thermal output refers to the manufacturer's laboratory environment
conditions and cannot be compared to measurements carried out in different locations. Measurement accuracy σ = +/- 1.5 dB(A).

STANDARD ACCESSORIES

Burner coupling flange gasket
Stud bolts
Hexagon nuts
Flat washers
Hoses
Filter
Copper gasket
³) DIESEL EMISSIONS
Classes defined according to EN 267 standards.
Class
1
2
3
MODEL
NOx emissions in mg/kWh diesel fuel
≤ 250
≤ 185
≤ 120
5 / 34
0006160448_202302
TBL 1200 ME
Kg/h
270
Kg/h
1012
kW
3200
kW
12000
mg/kWh
Class 2
1.5° E - 20° C
Electronic modulation
10 kV 30 mA - 230 V
kW
22
4
3L - 400V - 47,7A - 28,29kW
1N - 230V - 2,15A - 0,495kW
IP54
BT320
QRA 2
Servomotor
°C
-15 ÷ +40
dBA
89
kg
840
kg
550
TBL 1200 ME
1
N°8 M20
N°8 M20
N°8 Ø20
No.2 1"1/2
1"1/2
No. 2
CO emissions in mg/kWh diesel fuel
≤ 110
≤ 110
≤ 60
ENGLISH

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

36290010

Table of Contents