13.3 Response to Abnormal Grid Conditions

The inverter is designed to operate normally within the voltage and frequency ranges defined
by IEEE 1547-2003. Should grid conditions violate these limits, the inverter will cease to
energize within the required time. Once the grid conditions return to normal, the inverter will
then wait 5 minutes before attempting to reconnect. Tables 9.3 and 9.4 describe the standard
limits and clearing times. Other settings are available per the utility's request.
Protective Function
27-1
27-2
59-1
59-2
Protective Function
81O-1
81U-1
81U-2
DOCR- 070254-A
Voltage Pickup
V < 50%
V < 88%
V > 110%
V ≥ 120%
Table 13.3.1 – Response to Abnormal AC Voltage
Figure 13.3.2 –
Frequency Pickup (Hz)
f>60.5
f<57.0
f<{59.8-57.0} adjustable
f<59.3 standard
Table 13.3.2 – Response to Abnormal Frequency
Page 84 of 88
SGI 500XT
Clearing Time (s)
0.16
2.0
1.0
0.16
Clearing Time (s)
0.16
0.16
{.16-300} adjustable
0.16 standard