Safety chains and straps must be used to prevent any possible tilting or shifting
of the inverter in any direction while being lifted.
WARNING: Do not install the inverter on or over combustible surfaces or materials.
3.3

Removing Inverter From Pallet and Moving Inverter Into Place

It is recommended to keep the inverter secured to the pallet and moved as close as possible to
its final location prior to removing the pallet. To remove the securing bolts use a 9/16" socket
and/or wrench. Completely remove each bolt from the pallet.
The center of gravity of the inverter is marked with a label on the back of the enclosure.
Before lifting from the bottom, make sure lifting forks are located at the appropriate markers. If
the chase entry collars are installed, be sure to keep lifting forks clear of the collars or remove
collars to prevent damage. Install safety chains (with failsafe hooks) to prevent the inverter
from sliding off the lifting forks. If the inverter is lifted without the shipping pallet, a properly
rated safety strap must be placed over the top of the inverter firmly holding it down on the
lifting devices forks.
Use positions A when lifting or moving the inverter while attached to the pallet.
Use positions B when lifting or moving the inverter removed from the pallet.
DOCR- 070254-A
Figure 3.3.1 – Forklift Lifting Positions
Page 9 of 88