4 DC Connections from the PV Array and AC Connections to the Grid 
 
WARNING:  All electrical installations shall be performed in accordance with applicable 
local, state, and national electric codes. 
 
WARNING: Only connect the DC and AC power and grounding wires with the AC and DC 
disconnect  switches  off  and  the  circuits  isolated  from  AC  power  from  the  grid  and  DC 
power from the array.   
  
WARNING:  Make sure to connect the inverter and other exposed metal equipment in 
the  system  to  the  grounding  electrode  system  through  the  installation  of  the 
Grounding  Electrode  Conductor(s)  and  Equipment  Grounding  Conductors  before 
proceeding to connect any DC or AC power wires.  
 
WARNING:  Only  make  AC  connections  directly  to  the  lugs  within  the  AC  disconnect 
switch  and DC connections to the lugs within the DC disconnect switch. 
 
 
NOTE:    All  grounding  and  power  wiring  terminals  are  dual  rated  for  Copper  and 
Aluminum Wire.  When using aluminum wire exercise best industry practices to ensure 
a reliable connection; thoroughly clean the conductor just prior to making the electrical 
connection and use an oxide inhibitor to prevent the formation of aluminum oxide. 
 
NOTE:  Grounding and power wiring terminals are rated to 167°F (75ᵒC). 
 
NOTE:    When  conduit  hubs  are  used  for  DC  and  AC  cable  entry  in  an  outdoor  or  wet 
location,  rain‐tight  or  wet  location  hubs  that  comply  with  the  requirements  in  the 
Standard For Fittings For Conduit and Outlet Boxes, UL514B, are to be used. 
 
AC grounding and power connections are made in the AC disconnect switch of the inverter.  The 
type of AC disconnect switch provided with the inverter depends on the inverter power rating, 
output voltage, and fusing specified by the customer (i.e. fused or unfused).     
 
DC grounding and power connections are made in the DC disconnect switch of the inverter.  The 
type  of  DC  disconnect  switch  provided  with  the  inverter  depends  on  the  inverter  power  rating 
and DC overcurrent protection specified by the customer (i.e. fuses or breakers, amperage, and 
quantity).   
 
4.1 Grounding 
The PVI 50‐100KW inverter has grounding connection points in the DC and AC disconnect switches 
as  listed  below.    These  points  are  used  for  Grounding  Electrode  Conductor  (GEC)  and  Equipment 
Grounding Conductor (EGC) connections.   PV systems have EGC and GEC conductor requirements 
DOCR‐070233 
 
Page 14 of 92
PVI 50‐100KW Series Inverters 