PVI13KW
NOTE: Always use all 4 mounting tabs if wall mounted.
NOTE: The nearly 380 lb. weight of the inverter will exert as much as 100 lbs.
per bolt on the 4 wall mounts. Tension on the top bolts could also be 100 lbs.
Make sure an appropriate safety margin is used for both shear and tension of wall
mounting bolts, anchors or other attachments.
NOTE: If the roof/floor mounting only uses the inverter's mounting feet, be sure
you use all 4 available foot mount bolt positions. If a stand is used, be sure
inverter is securely mounted to stand, the stand is adequately designed for the
unit's weight and the stand is adequately attached to the floor/wall or roof.
NOTE: In the case of roof/floor mounting, temporary removal of disconnect
doors may facilitate easy wiring of the unit (only while wiring) however, only do
so if necessary and acceptable by local codes and applicable NEC requirements
related to your particular mounting configuration. (Do not ever leave disconnect
or main enclosure doors open when you are not actually working on the unit.)
2.3 DC Electrical Connection and AC Connection To
Building and Electrical Utility Grid
DOC-020028 rev 006
Fig. 3 Simplified electrical connection diagram