1. Remove backplane from enclosure prior to mounting (do not discard hardware).
2. Mark and predrill holes in the wall to line up with the top keyholes in the enclosure. Install the upper fasteners and screws in the wall.
with the screw heads protruding. Place the enclosure's upper keyholes over the screws; level and secure. Mark the position of the
lower holes. Remove the enclosure. Drill the lower holes and install the fasteners. Place the enclosure's upper keyholes over the
upper screws. Install the lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 10, 12).
3. Mount included UL Listed tamper switch(es) (Altronix Model TS112 or equivalent) in desired location, opposite hinge.
Slide the tamper switch bracket onto the edge of the enclosure approximately 2" from the right side (Fig. 1, pg. 3).
Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device.
To activate alarm signal open the door of the enclosure.
4. Mount Altronix/AMAG boards to backplane, refer to pages 4-6.
Hardware:
Metal or Nylon Standoff |
Trove2AG2 / Trove2AM2 / Trove3AM3
Installation Instructions for Trove2 / Trove3:
5/16" Pan Head Screw |
Lock Nut
Edge of
Enclosure
Tamper Switch
(provided)
To Access Control Panel or
UL Listed Reporting Device
Fig. 1
Enclosure
- 3 -