13: Backup Reporting (57); 14: Touchtone/Rotary Select (58); 15: Make Break Ratio (59); 16: Address (60) - Honeywell NOTIFIER UDACT Instruction Manual

Universal digital alarm communicator/transmitter
Table of Contents

Advertisement

Programming Instructions
NOTE: Use receive only selection when using remote annunciators. Be certain to set one of the
annunciators for receive/transmit for EIA-485 communications bus supervision. Use the
receive/transmit entry when annunciators are not installed or when the UDACT receive/transmit
function is to be used to supervise the EIA-485 communication bus. For more information on the
receive/transmit function, refer to annunciator manuals.
3.4.13 Backup Reporting (57)
Leaving address 57 at "0" means that reports will be transmitted to the secondary phone number
only if attempts to communicate to the primary phone number are unsuccessful. Programming a
"1" causes all reports to be transmitted to the secondary phone number.
3.4.14 Touchtone/Rotary Select (58)
A "0" programmed in this address by the factory triggers touchtone dialing over both telephone
lines.
Select "1" for rotary dialing.
3.4.15 Make Break Ratio (59)
Use this address only if you have chosen "1" for address 58. The make/break ratio is factory set to
"0" which is 67/33, but may be changed to "1" which is a 62/38 ratio.
3.4.16 Address (60)
Leave default of "0".
3.4.17 Address (61)
Leave default of "0".
3.4.18 AC Loss Reporting Delay (62)
"0" is the setting which causes immediate reporting of AC loss. Valid entries are 0 to 9 and A to F
corresponding to the following reporting delay times: "1" = 1 hour, "2" = 2 hours (factory default
setting), "3" = 6 hours, "4" = 7 hours, "5" = 8 hours, "6" = 9 hours, "7" = 10 hours, "8" = 11 hours,
"9" = 15 hours, "A" = 16 hours, "B" = 17 hours, "C" = 20 hours, "D" = 21 hours, "E" = 22 hours
and "F" = 23 hours.
3.4.19 Host Panel ID (63)
Enter one of the following digits corresponding to the Control Panel in which the UDACT is
installed. A correct entry is essential for proper operation.
0 = AFP-100
1 = System 500
2 = Do not use
3 = System 5000
4 = System 5000 with AIM-200
5 = NFS2-640, NFS-640, NFS-320
6 = AFP-200 (Factory Default Setting)
7 = AM2020/AFP1010, NCA, NCA-2, NFS-3030, NFS2-3030
34
UDACT Instruction Manual — P/N 50050:M 12/18/2009