5.1 Data Reporting Structure

The table below shows the data reporting structure for each of the pulsed formats as well as the
Ademco Express formats.
• Ademco Express formats allow a typical data message to be transmitted to the Central
Station in under 5 seconds.
• Pulsed formats typically require 15 to 20 seconds in comparison.
Table 5.2 on page 57 defines each letter code used in Table 5.1.
Table 5.3 on page 58 describes the data reporting structure used for Ademco Contact ID format.
Do not select any of the pulsed or Ademco Express Formats if identification of the specific zone or
point is desired. Use Ademco Contact ID for specific zone or point identification.
NOTE: Refer to Table 6 on page 61 for a list of compatible receivers.
56

Section 5: Reporting Formats

Report
Alarm
Alarm Restore
Zone Trouble
(Zone Open)
Zone Trouble Restore
System Trouble
System Trouble Restore
Low Battery
Low Battery Restore
AC Loss
AC Loss Restore
Supervisory Condition
Supervisory Condition Restore
Test Report
Abnormal Test Report
Table 5.1 Data Reporting Structure
Format #
Format #
0, 2, 4, 6, 8
1, A, C
3+1/4+1/Standard
4+2/Standard
4+1 Express
4+2 Express
SSS(S) A
SSSS AA2
SSS(S) RA
SSSS RARA2
SSS(S) RTZ
SSSS TZTZ2
SSS(S) RTZ
SSSS RTZRTZ2
SSS(S) TS
SSSS TSTS2
SSS(S) RTS
SSSS RTSRTS2
SSS(S) L
SSSS LL2
SSS(S) RL
SSSS RLRL2
SSS(S) P
SSSS PP2
SSS(S) RP
SSSS RPRP2
SSS(S) V
SSSS VV2
SSS(S) RV
SSSS RVRV2
SSS(S) X
SSSS XX2
SSS(S) XA
SSSS XAXA2