Telephone Connections - Honeywell NOTIFIER UDACT Instruction Manual

Universal digital alarm communicator/transmitter
Table of Contents

Advertisement

Installation and Wiring

2.4 Telephone Connections

Provision to connect to two independent telephone lines is available via two telephone jacks
labeled "PH1" (Primary) and "PH2" (Secondary). Telephone line control/command is possible via
double line seizure as well as usage of an RJ31X style interconnection. (RJ31X jacks must be
ordered separately).
NOTE: It is critical that the UDACT be located as the first device on the incoming telephone circuit
to properly function.
Important! The UDACT must not be used to dial a phone number that is call-forwarded per
requirements of UL 864 9th Edition.
Primary Lines-
Incoming Telco
Phone Lines
24
To Premise Phones
Green
Ring
Red
Tip
1 2 3 4 5 6 7 8
RJ31X
Jack
Primary Phone
Line - PH-1
Modular Female
Connectors
Figure 2.8 Wiring Phone Jacks
Green
Ring
Tip
Red
Ring
Tip
1 2 3 4 5 6 7 8
RJ31X
Jack
Shorting bars inside
jack removed during
male plug insertion
Secondary Phone
Line - PH-2
Seven foot Cable
MCBL-7
(order separately)
Male Plug
Connectors
UDACT Instruction Manual — P/N 50050:M 12/18/2009