H.3.2: Notes - Honeywell NOTIFIER UDACT Instruction Manual

Universal digital alarm communicator/transmitter
Table of Contents

Advertisement

AM2020/AFP1010 (UL 8th)
H.3.2 Notes
1.
Ferrite cores, PN 29090, are recommended for all applications.
2.
Recommended wire is 12 AWG (3.25mm
cable. Connect only one end of shield: a) shield may be connected to cabinet (earth ground) at
fire alarm panel, or b) shield may be connected to TB1 Terminal 5 (Shield) at UDACT as
shown in Figure H.1.
NOTE: The shield end that is not connected should be insulated to prevent accidental grounding.
Do not connect both ends of shield under any circumstance since a ground fault may result.
3.
Conduit is recommended for external wire runs. Consult local building codes.
4.
Refer to "Specifications" on page 13 for power requirements.
Below is a remote installation of a UDACT with an AM2020/AFP1010using an MPS-24A main
power supply:
EIA-485
Interface
BAT +
BAT -
+24R COMMON
CAB-3/4 Series Cabinet
104
Ferrite Cores
SIB-2048
POWER LIMITED
+24
COMMON
MPS-24A
DO NOT USE
Figure H.1 UDACT and AM2020/AFP1010 with MPS-24A
2
) to 18 AWG (0.75mm
To Phone Lines
(supervised)
ABS-8RB or UBS-1
+24V
GND
RS+
ACS/TERM
RS–
SHIELD
RS+
TERM
Rs–
UDACT Instruction Manual — P/N 50050:M 12/18/2009
Wiring
2
), twisted pair, shielded
Solid Earth
Ground
Connection
EARTH
Comm FAILURE
+24V