F.4: Type Mode Programming; F.4.1: For Zone Identification; F.4.2: For Point Identification - Honeywell NOTIFIER UDACT Instruction Manual

Universal digital alarm communicator/transmitter
Table of Contents

Advertisement

Type Mode Programming
Below is an internal installation of a UDACT with an NFS-640:
CPU-640 TB7
24VDC
nonresettable
power
F.4 Type Mode Programming
To disable or identify a zone or point in Type Mode (refer to "Type Mode" on page 52), the
following Entries/Addresses are used:
F.4.1 For Zone Identification:
Zones 1 - 99 are programmed by Entries/Addresses 01 - 99. The factory default code is 'fire alarm.'
F.4.2 For Point Identification:
NOTE: Loop 2 Programming is only available for the NFS2-640 and NFS-640.
Loop 1, Modules 1 - 64 are programmed by Type Mode Entries/Addresses 001 - 064
Loop 2, Modules 1 - 64 are programmed by Type Mode Entries/Addresses 065 - 128
Loop 1, Modules 65 - 128 are programmed by Type Mode Entries/Addresses 129 - 192
Loop 2, Modules 65 - 128 are programmed by Type Mode Entries/Addresses 193 - 256
Loop 1, Modules 129 - 159 are programmed by Type Mode Entries/Addresses 257 - 287 (288 not
used)
Loop 2, Modules 129 - 159 are programmed by Type Mode Entries/Addresses 289 - 319 (320 not
used)
Loop 1, Detectors 1 - 64 are programmed by Type Mode Entries/Addresses 321 - 384
Loop 2, Detectors 1 - 64 are programmed by Type Mode Entries/Addresses 385 - 448
Loop 1, Detectors 65 - 128 are programmed by Type Mode Entries/Addresses 449 - 512
Loop 2, Detectors 65 - 128 are programmed by Type Mode Entries/Addresses 513 - 576
UDACT Instruction Manual — P/N 50050:M 12/18/2009
Ferrite Core
-
+
CPU-640
TB13
ACS/TERM
DO NOT USE
Figure F.4 UDACT and NFS-640 in the Same Cabinet
NFS2-640, NFS-320, (UL 9th) and NFS-640 (UL 8th)
To Phone Lines
(supervised)
+24V
GND
RS+
RS–
SHIELD
RS+
TERM
Rs–
Connect to
Chassis
EARTH
Comm FAILURE
+24V
91