1: Telephone Circuitry; 2: Digital Communicator; 3: Telephone Company Rights And Warnings - Honeywell NOTIFIER UDACT Instruction Manual

Universal digital alarm communicator/transmitter
Table of Contents

Advertisement

Overview
1.11.1 Telephone Circuitry
Ringer Equivalence Number (REN) = 0.6B
The REN is used to determine the quantity of devices which may be connected to the telephone
line. Excessive REN on the telephone line may result in the devices not ringing in response to an
incoming call. In most, but not all areas, the sum of the REN should not exceed five (5.0). To be
certain of the number of devices that may be connected to the line, as determined by the total REN,
contact the telephone company to determine the maximum REN for the calling area.
1.11.2 Digital Communicator
Before connecting the UDACT to the public switched telephone network, the installation of two
RJ31X jacks is necessary. The following information is provided if required by the local telephone
company:
Important! The UDACT must not be used to dial a phone number that is call-forwarded per
requirements of UL 864 9th Edition.
1.11.3 Telephone Company Rights and Warnings
The telephone company under certain circumstances may temporarily discontinue services and/or
make changes in its facilities, services, equipment or procedures which may affect the operation of
this control panel. However, the telephone company is required to give advance notice of such
changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right
to temporarily discontinue service. Advance notification will be provided except in cases when
advance notice is not practical. In such cases, notification will be provided as soon as possible. The
opportunity will be given to correct any problems and to file a complaint.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY
LINE SERVICES..
When the control panel activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same
telephone line.
The control panel must be connected to the public switched telephone network upstream of any
private telephone system at the protected premises.
An FCC compliant telephone cord must be used with this equipment. This equipment is designed to
be connected to the telephone network or premises wiring using a compatible RJ31X male modular
plug which is Part 68 compliant.
14
AC Impedance 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: less than 4.0 volts for 2 minutes
Manufacturer:
Product Model Number:
FCC Registration Number:
Ringer Equivalence:
Telephone Requirements and Warnings
Honeywell Life Safety
12 Clintonville Road
Northford, CT 06472
UDACT
1W6USA-20723-AL-E
0.6B
UDACT Instruction Manual — P/N 50050:M 12/18/2009