Break Tabs
Communications
Loop
Connections
Contact
Connections
Contact Ratings
30 Addressable Intelligent Module—AIM -200 Addressable Intelligent Module
Figure 24: M510CJ Control Module (Form -C Relay)
To configure a M510CJ as a Form -C relay, the two tabs must be broken
off of the module. Use a pair of needle -nose pliers to break off each tab.
Connect the communications loop to M510CJ Terminals 1( -) and 2 (+).
The M510CJ occupies one module address on the loop. Set the rotary
switches on the M510CJ to the particular loop address required.
Wire the common and the normally -open or normally -closed contacts to
the M510CJ as needed.
Resistive: 2 amps @ 30 VDC
Inductive: 1 amp @ 30 VDC (0.6 pf)
0.3 amps @ 120 VDC (0.35 pf)
Contacts are not rated for pilot duty or motor loads.