Induction Range
Planning Information
Follow all minimum clearances to combustible surfaces
shown in the illustration on the following page.
78 | English
ELECTRICAL REQUIREMENTS
Installation must comply with all applicable electrical
codes and be properly grounded (earthed).
Locate the electrical supply flush with the wall or floor
and within the shaded area shown in the illustration on the
following page. A separate circuit servicing only this appli-
ance is required.
If a power supply cord is used, the cord must be desig-
nated for use with ranges and rated for 240 V, 50 amps,
and must include 3 or 4 conductors.
Performance may be compromised if the electrical supply
is less than 240 volts.
ELECTRICAL REQUIREMENTS
ELECTRICAL SUPPLY
Single Phase
3-Phase
MAX CONNECTED LOAD
76 cm Range
91 cm Range
220–240 V AC, 50/60 Hz
380–415 V AC, 50 Hz
SINGLE PHASE
3-PHASE
50 A
19 A
60 A
33 A