5-6
Measurement Functions

Power Calculation

857-UM001A-EN-P – July 2009
"1LL+U
/LLy"
0
This mode is used with the synchrocheck function. See
Table 3.40.
"2LL/LLy"
This mode is used with the synchrocheck function. See
Table 3.40
"LL/LLy/LLz"
This mode is used with the synchrocheck function. See
Table 3.40.
The overvoltage protection is always based on the line-to-line
voltage regardless of the measurement mode.
The power calculations in Allen-Bradley devices are dependent on
the voltage measurement mode (see "Voltage Measurement Mode").
The equations used for power calculations are described in this
chapter.
The device is connected to line-to-line voltages
When the device is connected to line-to-line voltages, the voltage
measurement mode is set to equal to "2LL+Uo". The following Aron
equation is used for power calculation.
=
*
S
U
I
U
12
L
1
23
=
Three phase power phasor
S
=
Measured voltage phasor corresponding the
U
12
fundamental frequency voltage between
phases L1 and L2.
*
=
Complex conjugate of the measured phase L1
I
1 L
fundamental frequency current phasor.
=
Measured voltage phasor corresponding the
U
23
fundamental frequency voltage between
phases L2 and L3.
=
Complex conjugate of the measured phase L3
*
I
L
3
fundamental frequency current phasor.
Apparent power, active power and reactive power are calculated as
follows:
=
S
S
=
P
real
(
S
)
=
Q
imag
(
S
)
P
ϕ
=
cos
S
*
I
, where
L
3