3-12
Protection Functions
857-UM001A-EN-P – July 2009

Four independent stages

There are four separately adjustable stages available: I
I
>>> and I
>>>>.
dir
dir

Inverse operation time

Stages I
> and I
>> can be configured for definite time or
dir
dir
inverse time characteristic. See chapter Error! Reference
source not found. for details of the available inverse delays.
Stages I
>>> and I
>>>> have definite time (DT) operation
dir
dir
delay. The device will show a scaleable graph of the configured
delay on the local panel display.

Inverse time limitation

The maximum measured secondary current is 50xI
the scope of inverse curves with high pick-up settings. See
"Inverse Time Operation" for more information.

Cold load and inrush current handling

See "Cold Load Pick-up and Inrush Current Detection" in Chapter 4.

Setting Groups

There are two settings groups available for each stage. Switching
between setting groups can be controlled by digital inputs, virtual
inputs (mimic display, communication, logic) and manually.
Figure 3.10 shows the functional block of the Idir> stage.
Figure 3.10 – Block Diagram of the three-phase Overcurrent Stage I
>, I
>>,
dir
dir
. This limits