Allen-Bradley Rockwell Automation 857 User Manual page 24

Hide thumbs Also See for Rockwell Automation 857:
Table of Contents

Advertisement

2-8
Local Panel User Interface
857-UM001A-EN-P – July 2009
Table 2.2 – List of the Local Main Menu (cont.)
Main
Number
Menu
of Menus
I<
3
Undercurrent stage
I2>
3
Current unbalance stage
T>
3
Thermal overload stage
Io>
5
1st earth fault stage
Io>>
3
2nd earth fault stage
Io>>>
3
3rd earth fault stage
Io>>>>
3
4th earth fault stage
6
1st directional earth fault stage
Ioϕ>
6
2nd directional earth fault stage
Ioϕ>>
Ioint>
4
Transient intermittent E/F
U>
4
1st overvoltage stage
U>>
3
2nd overvoltage stage
U>>>
3
3rd overvoltage stage
U<
4
1st undervoltage stage
U<<
3
2nd undervoltage stage
U<<<
3
3rd undervoltage stage
Uo>
3
1st residual overvoltage stage
Uo>>
3
2nd residual overvoltage stage
P<
3
1st reverse and underpower stage
P<<
3
2nd reverse and underpower stage
f><
4
1st over/under-frequency stage
f>><<
4
2nd over/under-frequency stage
f<
4
1st underfrequency stage
f<<
4
2nd underfrequency stage
dfdt
3
Rate of change of frequency (ROCOF) stage
Prg1
3
1st programmable stage
Prg2
3
2nd programmable stage
Prg3
3
3rd programmable stage
Prg4
3
4th programmable stage
Prg5
3
5th programmable stage
Prg6
3
6th programmable stage
Prg7
3
7th programmable stage
Prg8
3
8th programmable stage
CBFP
3
Circuit breaker failure protection
CBWE
4
Circuit breaker wearing supervision
AR
15
Auto-reclose
CTSV
1
CT supervisor
VTSV
1
VT supervisor
ArcI>
4
Optional arc protection stage for phase-to-phase faults
and delayed light signal.
Description
ANSI
Note
code
37
4
46
4
49
4
50N/51N
4
50N/51N
4
50N/51N
4
50N/51N
4
67N
4
67N
4
67NI
4
59
4
59
4
59
4
27
4
27
4
27
4
59N
4
59N
4
32
4
32
4
81
4
81
4
81L
4
81L
4
81R
4
4
4
4
4
4
4
4
4
50BF
4
4
79
4
4
50ARC
4

Advertisement

Table of Contents
loading

Table of Contents