Opening Access

1. Push the INFO key and the ENTER key on the front panel.
ENTER PASSWORD
0
***
Figure 2.15 – Opening the Access Level
2. Enter the password needed for the desired level: the password
can contain four digits. The digits are supplied one by one by
first moving to the position of the digit using the RIGHT key and
then setting the desired digit value using the UP key.
3. Push the ENTER key.

Password Handling

The passwords can only be changed using SetPointPS software
connected to the local RS-232 port on the relay.
It is possible to restore the password(s) in case the password is lost or
forgotten. In order to restore the password(s), a relay program is
needed. The serial port settings are 38400 bps, 8 data bits, no parity
and one stop bit. The bit rate is configurable via the front panel.
Command
get pwd_break
get serno
Send both the numbers to Rockwell Automation and ask for a password
break. A device specific break code is sent back to you. That code
will be valid for the next two weeks only for this specific device.
Command
set pwd_break=4435876
Now the passwords are restored to the default values (See section
"Operating Levels").
Local Panel User Interface
Description
Get the break code (Example: 6569403)
Get the serial number of the relay (Example: 12345)
Description
Restore the factory default passwords ("4435876" is
just an example. The actual code should be
requested from Rockwell Automation.)