Table 3.24 – Measured and recorded values of capacitor bank unbalance
protection: I
>, I
>> (50N/51N)
02
02
Parameter
Value
Measured
Io
values
dIo
Display
Io>>>, Io>>>>
Recorded
SCntr
values
TCntr
Flt
EDly
Isaved
SavedA
Faults (Io>>>>
only)
Total
(Io>>>> only)
Clear
(Io>>>> only)
L1-B1 (Io>>>>
only)
L1-B2 (Io>>>>
only)
L2-B1 (Io>>>>
only)
L2-B2 (Io>>>>
only)
L3-B1 (Io>>>>
only)
L3-B2 (Io>>>>
only)
Locat
(Io>>>> only)
LocAng (Io>>>>
only)
Protection Functions
Unit
Default
Pu
unbalance current
(including the natural unbalance
current)
A
Compensated unbalance current
A
Setting value
-
Cumulative start counter
-
Cumulative trip counter
pu
The max. fault value
%
Elapsed time as compared to the set
operating time; 100% = tripping
A
Recorded natural unbalance current
deg
Recorded phase angle of natural
unbalance current
-
Allowed number of element failures
-
Actual number of element failures in
the bank
-, Clear
-
Clear the element counters
-
Number of element failures in phase
L1 in brach 1 (left side)
-
Number of element failures in phase
L1 in brach 2 (right side)
-
Number of element failures in phase
L2 in brach 1 (left side)
-
Number of element failures in phase
L2 in brach 2 (right side)
-
Number of element failures in phase
L3 in brach 1 (left side)
-
Number of element failures in phase
L3 in brach 2 (right side)
-
Changed unbalance current (after
automatic compensation)
-
Changed phase angle of the
unbalance current (after automatic
compensation)
3-43
Description
857-UM001A-EN-P – July 2009