Table 3.30 – Parameters of the under voltage stages U<, U<<, U<<< (27) (cont.)
Parameter
Value
Force
Off
On
MinU
U<, U<<,
U<<<
U<, U<<,
U<<<
t<, t<<, t<<<
LVBlk
RlsDly
Hyster
Default 3.0
%
For details of setting ranges, see "Protection Stages" in Chapter 10.
Set = An editable parameter (password needed)
C = Can be cleared to zero
F = Editable when force flag is on

Recorded values of the latest eight faults

Detailed information is available on the eight latest faults for each of
the stages: Time stamp, fault voltage, elapsed delay, voltage before
the fault and setting group.
Table 3.31 – Recorded values of the undervoltage stages (8 latest faults)
U<, U<<, U<<< (27)
Parameter
Value
yyyy-mm-dd
hh:mm:ss.ms
Flt
EDly
PreFlt
SetGrp
1
2
Protection Functions
Unit
Description
Force flag for status forcing for test
purposes. This is a common flag for
all stages and output relays, too.
Automatically reset by a 5-minute
timeout.
V
The supervised minimum of line-to-line
voltages in primary volts
V
Pick-up value scaled to primary value
%Un
Pick-up setting
S
Definite operation time
%Un
Low limit for self blocking
S
Release delay (U< stage only)
%
Dead band setting
Unit
Description
Time stamp of the recording, date
Time stamp, time of day
%Un
Minimum fault voltage
%
Elapsed time of the operating time setting.
100% = trip
%Un
Supervised value before fault, 1 s average
value.
Active setting group during fault
3-55
Note
Set
Set
Set
Set
Set
Set