4-10
Supporting Functions
Current Transformer
Supervision
857-UM001A-EN-P – July 2009
Table 4.7 – Setting Parameters of the Voltage Sag Measurement Function
Parameter
Value
U1<
10.0 ... 120.0
Period
8h
Day
Week
Month
Date
Time
Table 4.8 – Measured and Recorded Values of Voltage Sag Measurement Function
Parameter
Measured
Voltage
value
U1
Recorded
Count
values
Prev
Total
Prev
The device supervise the external wiring between the device
terminals and current transformers (CT) and the CT them selves.
Furthermore, this is a safety function as well, since an open
secondary of a CT, causes dangerous voltages.
The CT supervisor function measures phase currents. If one of
the three phase currents drops below I
phase current is exceeding the I
issue an alarm after the operation delay has elapsed.
Table 4.9 – Setting Parameters of CT Supervisor: CTSV ( )
Parameter
Value
Imax>
0.0 ... 10.0
Imin<
0.0 ... 10.0
t>
0.02 ... 600.0
CT on
On; Off
CT off
On; Off
Unit
Default
%
64
Setting value
-
Month
Length of the observation period
-
-
Date
-
-
Time
Value
Unit
LOW;
-
Current voltage status
OK
%
Measured positive sequence
voltage
-
Number of voltage sags during
the current observation period
-
Number of voltage sags during
the previous observation period
s
Total (summed) time of voltage
sags during the current
observation period
s
Total (summed) time of voltage
sags during the previous
observation period
< setting, while another
min
> setting, the function will
max
Unit
Default
xIn
2.0
Upper setting for CT supervisor
xIn
0.2
Lower setting for CT supervisor
s
0.10
Operation delay
-
On
CT supervisor on event
-
On
CT supervisor off event
Description
Description
Description